Read Rules - Configuration Example
Create an RTU Read Rule for the ISM Radio of a DXM1200-B2 or -X2
Follow these steps to create a new read rule to access data from devices connected to the radio of a DXM1200-B2 or
DXM1200-X2.
This example creates a read rule to read six registers (1 through 6), from the radio (port 5) at Modbus ID 1. The results are
stored in the Local Registers 1 through 6.
From the Register Mapping
›
RTU
›
RTU Read screen, click Add Read Rule.
1.
Click the arrow next to the name to display the parameters.
2.
Name your rule.
3.
Select the device ID.
4.
Select how many registers to read, and the beginning register.
5.
Define the register type, how often to read the register, and any other appropriate parameters.
6.
If necessary, select the error condition. For this example, if the read function fails after three attempts, the read rule
writes 12345 to the DXM local registers. Notice the list of local register names this read rule is using.
7.
Define the port settings to be compatible with the connected devices.
1.
Go to the Register Mapping
›
RTU
›
RTU Configuration screen.
a.