Technical data • Individual components
84
Panel PC 800 User's Manual V1.30
3.8.4.3.3 POWERLINK station number
POWERLINK station number (x1, x16)
Both of these hex switches (x16, x1) are used to configure the POWERLINK station
number. Station numbers between #00 and #FD are permitted.
Switch position
x1
x16
Description
0
0
Operation as managing node
1 ... D
0 ... F
station number Operation as controlled node
E
F
Reserved
F
F
Reserved
Station number
x1
Station number
x16
Table 63: POWERLINK station number (x1, x16)
3.8.4.3.4 Card number switch
The one-digit card number ($1 – $F) is configured using the card number switch. This number is used to identify
the module.
Card numbers
switch
Figure 28: POWERLINK card - 2-port node number switch
If the card is operated with Automation Runtime, then the card number switch must match the slot number in
Figure 29: Integrating the POWERLINK plug-in card in Automation Studio
3.8.4.3.5 SRAM
The 2-port 5ACPCC.MPL0-00 POWERLINK card has 512 kB SRAM.