Technical data
Panel PC 2100 user's manual V1.17
173
2.3.5.3 5ACCIF01.FPLK-000
2.3.5.3.1 General information
Interface option 5ACCIF01.FPLK-000 is equipped with 2 female RJ45 connectors connected to an integrated POW-
ERLINK hub. 512 kB of nvSRAM is also installed.
The integrated 2-port hub allows for the easiest possible implementation of a simple tree structure, daisy chain
wiring or optional ring redundancy without extra effort.
With pollresponse chaining (PRC), the IF option offers a solution for the highest demands on response time and
the shortest cycle times. When combined with the B&R control system, poll-response chaining provides ideal
performance, particularly for central control tasks.
•
1x POWERLINK interface for real-time communication
•
512 kB nvSRAM
•
Integrated hub for efficient cabling
•
Configurable ring redundancy
•
Poll-response chaining
•
Compatible with APC2100/PPC2100 and APC2200/PPC2200
This interface option can only be operated with Automation Runtime.
Information:
Ring redundancy and simultaneous poll-response chaining operation is not possible with this IF op-
tion.
2.3.5.3.2 Order data
Model number
Short description
Figure
Interface options
5ACCIF01.FPLK-000
Interface card - 1x POWERLINK interface - Integrated 2-port
hub - 512 kB nvSRAM - For APC2100/PPC2100/APC2200/
PPC2200 - Only available with a new device
Table 146: 5ACCIF01.FPLK-000 - Order data
2.3.5.3.3 Technical data
Information:
The following specifications, properties and limit values apply only to this accessory and may deviate
from those that apply to the complete system. For the complete system in which this accessory is
installed, for example, the data specified for that complete system applies.
Model number
5ACCIF01.FPLK-000
General information
LED status indicators
L1, L2, L3
B&R ID code
0xE9BA
Certifications
CE
Yes
UL
cULus E115267
Industrial control equipment
HazLoc
cULus HazLoc E180196
Industrial control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T4
1)
Controller
nvSRAM
Size
512 kB
Data retention
20 years
Read/Write endurance
Min. 1,000,000
Remanent variables in power failure mode
256 kB
(e.g. for Automation Runtime, see Automation Help)
Table 147: 5ACCIF01.FPLK-000 - Technical data