110
Technical data • Entire device
Automation PC 620 with 945GME N270 CPU board User's Manual V 1.10
2.13.9 POWERLINK station number (only APC620 embedded)
2.13.10 Ethernet connection ETH (only APC620 embedded)
This Ethernet connection is integrated in the CPU board being used.
POWERLINK station number (x1, x16)
Both of these hex switches (x16, x1) are used to configure the
station number for the POWERLINK. Station numbers are
permitted between #00 and #FD.
Switch position
x16
x1
Description
0
0
Operation as managing node
0 ... F
1 ... D
station number Operation as controlled
node
F
E
Reserved
F
F
Reserved
Table 40: POWERLINK station number (x1, x16) - only APC620 embedded
Ethernet connection ETH (only APC620 embedded)
Controller
Intel 82562
RJ45 twisted pair (10BaseT/100BaseT), female
Cabling
S/STP (Cat5e)
Transfer rate
10/100 MBit/s
1)
1) Both operating modes possible. Change-over takes place automatically.
Cable length
max. 100 m (min. Cat5e)
LED
On
Off
Green
100 Mbit/s
10 Mbit/s
Orange
Link
(Ethernet network
connection
available)
Activity (blinking)
(Data transfer in
progress)
Table 41: Ethernet connection ETH (only APC620 embedded)
green
orange
Summary of Contents for 5PC600.SE00-00
Page 2: ...2 Automation PC 620 with 945GME N270 CPU board User s Manual V 1 10...
Page 4: ...4 Automation PC 620 with 945GME N270 CPU board User s Manual V 1 10...
Page 6: ...6 Automation PC 620 with 945GME N270 CPU board User s Manual V 1 10...
Page 568: ...568 Appendix A Glossary Automation PC 620 with 945GME N270 CPU board User s Manual V 1 10...