Installation and wiring
5.4 Switch the link module
1. Disconnect the power supply cable to the Automation Panel (disconnect the power cable). Disconnect from
all sources and poles!
2. Carry out electrostatic discharge at the ground connection.
3. Remove the Automation Panel from the control cabinet by following the installation steps in reverse order.
4. Place the Automation Panel on a clean, flat surface.
5. Remove the Torx screws (T10) indicated in the following figure.
Figure 11: Removing the Torx screws
6. The link module can now be removed by pulling it straight up.
Figure 12: Removing the link module
7. The link module can now be reinstalled by following these steps in reverse order. The max. tightening torque
of the Torx screws (T10) is 0.5 Nm.
5.5 Connecting to the power grid
Danger!
•
The entire power supply must be disconnected and electrostatic discharge must take place on
the housing or ground connection before removing any covers or components from the device
and installing or removing any accessories, hardware or cables.
•
Remove the power cable from the device and from the power supply.
•
All covers and components, accessories, hardware and cables must be installed or secured
before the device is connected to the power supply and switched on.