Do not connect the ground to the neutral (N) leg at the terminal strip (if so equipped).
If a DELTA supply system is used, the high leg should be connected to L3, since control voltage is
derived from L1 and L2.
Note:
Ensure that all power connections are tight. Loose connections will
cause burned wires and contactors on electrically heated machines.
Check the electrical connections at the incoming power terminal block,
contactors, and heating elements at installation, after the first week of
operation, and quarterly thereafter. Failure of switchgear due to negli-
gence in this area is not covered under any warranty!
Table 3.2: Electrical Requirements
Electrical Requirement - Electrical Heating
Model
IC-1355
IC-1363
IC-1379
Motor Power (kW / HP)
0.37 / 0.5
0.37 / 0.5
0.49 / 0.75
Heating Power (kW)
12
16
21
Max kVA
15.5
20.5
27
Breaker Size
380-460V
20
30
40
208-230V
40
50
80
Cable Size (mm
2
/ AWG)
380-460V
4 / 10
4 / 10
16 / 5
208-230V
6 / 9
10 / 7
35 / 2
Electrical Requirements - Gas Heating
Model
IC-1355
IC-1363
IC-1379
Motor Power (kW / HP)
0.37 / 0.5
0.37 / 0.5
0.49 / 0.75
Max kVA
1
1
1
Breaker Size
380-460V
10
10
10
208-230V
10
10
10
120V
15
15
15
Cable Size (mm
2
/ AWG)
380-460V
2.5 / 14
2.5 / 14
2.5 / 14
208-230V
2.5 / 14
2.5 / 14
2.5 / 14
120V
2.5 / 14
2.5 / 14
2.5 / 14
3.4
Gas Connection
3.4.1
Gas Supply Line
•
1” IPS pipe is recommended.
9