SENSOR CONFIgURATION

PRODUCT 

Select corresponding sensor for: free chlorine, total
chlorine, chlorine dioxide, ozone, hydrogen peroxide, 
peracetic acid

UNIT 

Choose between: ppm / g/L

x-x.xxx ppm 

Decimal point (coma) position

SCALE 

MAXI: 00.00 

Maximal value of the measuring scale 

SENSOR

mA  or  mV

SAVING ? 

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

MENU

+

Next menu:

ADJUST ALARM 1

INTRODUCTION TO BAMOPHOX CONTROL

Before setting up alarms or way of control, the running way has to be defined.

Bamophox 194 allows you three ways:

l

Single alarms with alarms S1 and/or S2

l

Relay regulation with set point, proportional bands and dead zones

l

P.I.D. regulation with the 4-20 mA signal

There is a specificity of alarm 3 in Bamophox 194. It can be setup for an external sensor. Signal is coming from an
inductive flow rate sensor type NPN. This sensor is mounted in the flow cell.

Sensor signal entering Bamophox 194 activates or deactivates S3 alarm:

l

In case of flow rate, alarm 3 is closed (active)

l

In miss of flow rate, alarm 3 is open (inactive)

This signal will act on the regulation like following:

l

If the user is running with single alarms, there will be no more action on alarms S1 and/or S2.  
However user can wire alarms S1 and S3 in serial way in the aim of securing the injection (if alarm 1 deals with the
reagent injection)

l

If the user is running in relay regulation, alarms S1 and S2 become open (inactive). 
The regulation is inhibited.

l

If the user is running P.I.D regulation, 4-20mA signal become locked.

Summary of Contents for BAMOPHOX 194

Page 1: ...MES 194 01 1 Amperometric signal monitor BAMOPHOX 194 13 12 2013 194 M1 01 F INSTRUCTIONS MANUAL BAMOPHOX 194 Amperometric sensors signal monitor...

Page 2: ...ONT PANEL 7 SCROLLING MENU 8 ABOUT BAMOPHOX 9 CONSULTING MODIFYING 9 TESTING RELAY OUTPUTS 9 SENSOR CONFIGURATION 10 ADJUSTING THRESHOLD 1 11 ADJUSTING THRESHOLD 2 11 ADJUSTING THRESHOLD 3 12 ON OFF R...

Page 3: ...C depending of switching frequency ambient conditions accuracy Mechanical life time minimum 5 x106 operations 180 commutation min Electrical life time minimum 2 x105 20 comm min 3 A 125 V AC 3 A 30 V...

Page 4: ...M1 01 F 12 13 2013 WALL MOUNTINg INSTRUMENT 3 WIRINg OPTION LOGGER RS 422 OPTION LOGGER access by upper cover RS 422 PANEL MOUNTINg INSTRUMENT 29 30 31 36 V V 0V E Signal input Signal input 29 30 31 3...

Page 5: ...ntact Measurement Temperature S3 threshold NO contact Measurement Temperature External sensor NOT USED Ground N Main power supply N Neutral L Line L V V 0V E 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17...

Page 6: ...SENSOR CONNECTION Load resistor supplied with the BAMOPHOX 194 4 20 mA sensor 0 0 to 2000 mV sensor TERMINAL FOR SENSOR CONNECTION Flow rate sensor 194 832 NPN type normally open Brown Blue Black outp...

Page 7: ...his key all parameters are saved previous data programmation will be overwrited If you are not sure of any modification do not press the VALID key To change parameters of data capture Num ric input in...

Page 8: ...ADJUST ALARM 1 ADJUST ALARM 2 ADJUST ALARM 3 RELAY REGULATION REGUL PID OUTPUT mA MES OUTPUT mA TEMP TEMPERATURE SENSOR CALIBRATION FORCED RELAY ADJUST ALARM CLOCK RECORDING TIME LANGUAGE MENU MENU M...

Page 9: ...the configuration thresholds regulation analog outputs When PID regulation is activated the display shows the PID FORCED PID 00 00 ppm 00 00 One digit is flashing Modify the value Immediately the inst...

Page 10: ...D regulation with the 4 20 mA signal There is a specificity of alarm 3 in Bamophox 194 It can be setup for an external sensor Signal is coming from an inductive flow rate sensor type NPN This sensor...

Page 11: ...e contact S1 SAVINg ADJUST ALARM 2 ALARM 2 ON OFF ALARM 2 MEASURE TEMP MEASURE Threshold against measured value TEMP Threshold against temperature measured value ALARM 2 LOW HIgH HIgH Contact closes w...

Page 12: ...he limit LOW Contact closes when the value goes under the limit ON 00 00 ppm To close the contact S3 at this value OFF 00 00 ppm To open the contact S3 at this value DELAY UP ONI OFF Delay or no delay...

Page 13: ...est value for LOW PB 00 00 ppm proportional bandwith Highest value H IGH DZ 00 00 ppm for dead zone Lowest value LOW DZ 00 00 ppm for dead zone SAVING ENTER ENTER ENTER ENTER ENTER ENTER ENTER ENTER E...

Page 14: ...tion contact S1 is closed Inside the dead zone between 1 4 1 9 ppm S1 and S2 are OFF no injection at all contacts S1 and S2 are opened If the measurement value is between the dead zone and the highest...

Page 15: ...such as m Cde t delay of response T Time corresponding to the same variation in of measurement m and the analog output Cde m Cde This value may be found out on the slope Modify the PID parameters as f...

Page 16: ...Page 16 194 M1 01 F 12 13 2013 ppm measurement...

Page 17: ...lue corresponding to 00 00 or 04 00 mA OUTPUT 4 20 mA 0 20 mA Output type SAVING ENTER ENTER ENTER ENTER VALID TEMPERATURE AUTO A Pt 100 probe should be connected MEASURE AUTO MANUAL MANUAL Without Pt...

Page 18: ...ARD is displayed Proceed at the same time to a test to know the standard value according to the sensor in use Enter the result value For good calibration value has to be as closed as the sensor full r...

Page 19: ...g a malfunction on S1 and S2 contacts an overtime contact could be set up WITH WHITHOUT ALARM TMAX S1 0000 Sec Over timing on S1 closed contact maximum time for active relay TMAX S2 0000 Sec Over timi...

Reviews: