A
B
C
D
E
TBL 85P - 85P DACA
2 ÷ 2,5
19
5 2 ÷ 3 7,5 ÷ 8,5
TBL 105P - 105P DACA
2 ÷ 2,5
19
5 2 ÷ 3 7,5 ÷ 8,5
TBL 130P - 130P DACA
2 ÷ 2,5
19
5 2 ÷ 3 7,5 ÷ 8,5
TBL 160P - 160P DACA
2 ÷ 2,5
19
5 2 ÷ 3 7,5 ÷ 8,5
TBL 210P
12 ÷ 12,5 29 15 2 ÷ 3 7,5 ÷ 8,5
N°
00
02
93
51
31
18 / 28
0006081325_201210
ENGLISH
Legend:
1- Diffuser
2- Deflector disk
3- Nozzle holder
4- Ignition electrodes
5- Nozzle
ELECTRODES/IONISATION PROBE
ADJUSTMENT DIAGRAM
After having installed the nozzle, check the correct position of the
electrodes and disk according to the following levels. It’s adviseable
to check levels after every intervention on head.
!
To prevent damage to the support effect nozzle assembly/
disassembly tasks with the aid of a wrench and counter-
wrench.
!
The use of an ionisation angle of 45° may significantly
improve combustion values with certain applications (e.g.
narrow
combustion chambers).
RECOMENDED NOZZLES
MONAMRCH tipo PLP 60° (TBL 85P)
MONARCH tipo PLP 60° (TBL 105P)
MONARCH tipo PLP 60° (TBL 130P)
STEINEN tipo SS 45° (TBL 160P)
STEINEN tipo SS 45° (TBL 210P)
Summary of Contents for TBL 105P
Page 2: ......
Page 26: ...26 28 0006081325_201210 ENGLISH ELECTRIC DIAGRAM ...
Page 27: ...27 28 0006081325_201210 ENGLISH ...
Page 52: ...26 28 0006081325_201210 ESPAÑOL ESQUEMA ELECTRICO ...
Page 53: ...27 28 0006081325_201210 ESPAÑOL ...
Page 78: ...26 28 0006081325_201210 FRANÇAIS SCHEMA ELECTRIQUE ...
Page 79: ...27 28 0006081325_201210 FRANÇAIS ...
Page 104: ...26 28 0006081325_201210 DEUTSCH SCHALTPLAN ...
Page 105: ...27 28 0006081325_201210 DEUTSCH ...
Page 107: ......