10 / 28
0006081325_201210
ENGLISH
H = Difference in level between level in the tank and the pump axis.
L = Maximum length of suction pipe including the vertical lift. For each bend or valve deduct 0,25 m.
GRAVITY SUPPLY SYSTEM
1 Tank
2 Feeding pipe
3 Wire-net filter
4 Pump
5 Degasifier
6 Suction pipe
7 Return pipe
8 Automatic fuel interception
device at burner shut off
9 Non-return valve
PUMP AXIS
DROP-TYPE SYSTEM WITH SUPPLY FROM THE TANK TOP
PUMP AXIS
SUCTION - TYPE FEEDING SYSTEM
1 Tank
3 Wire-net filter
4 Pump
6 Suction pipe
7 Return pipe
10 Bottom valve
PUMP AXIS
N.B.
For any missing devices in the piping, follow existing regulations.
P = 3,5 m. (max.)
PIPES FOR LIGHT OIL BURNER MODEL TBL 130P/ P DACA - 160P/ P DACA - 210P
H
Total meters
meters
meters
Ø i. 16 mm.
1
40
1,5
45
2
45
2,5
50
3
50
H
Total meters
meters
meters
Ø i. 16 mm.
1
40
1,5
45
2
45
2,5
50
3
50
1 Tank
3 Wire-net filter
4 Pump
6 Suction pipe
7 Return pipe
8 Automatic fuel interception device at
burner shut off
9 One-way valve
10 Bottom valve
H
meters
Total meters
meters
Ø i. 14 mm.
Ø i. 16 mm.
0,5
36
55
1
30
48
1,5
25
41
2
20
32
2,5
15
24
3
10
15
3,5
4
7,5
Summary of Contents for TBL 105P
Page 2: ......
Page 26: ...26 28 0006081325_201210 ENGLISH ELECTRIC DIAGRAM ...
Page 27: ...27 28 0006081325_201210 ENGLISH ...
Page 52: ...26 28 0006081325_201210 ESPAÑOL ESQUEMA ELECTRICO ...
Page 53: ...27 28 0006081325_201210 ESPAÑOL ...
Page 78: ...26 28 0006081325_201210 FRANÇAIS SCHEMA ELECTRIQUE ...
Page 79: ...27 28 0006081325_201210 FRANÇAIS ...
Page 104: ...26 28 0006081325_201210 DEUTSCH SCHALTPLAN ...
Page 105: ...27 28 0006081325_201210 DEUTSCH ...
Page 107: ......