INSTRUCTIONS FOR DETERMINING THE CAUSE LEADING TO IRREGULARITIES IN THE
OPERATION AND THEIR ELIMINATION
IRREGULARITY
The equipment locks out with the flame on
(red lamp on). The fault is in the flame con
-
trol device.
The equipment goes into lock-out spraying
liquid fuel but the flame does not ignite (red
light on).
The equipment goes to lock-out without
spraying fuel.
The burner does not start.(The equipment
does not perform the start up program).
POSSIBLE CAUSE
1 Flame sensor off or soiled with smoke
2 Insufficient draught.
3 Flame sensor circuit interrupted in the
equipment.
4 Dirty flame disk and diffuser.
1 Ignition circuit severed.
2 The ignition transformer cables are
discharging to ground.
3 The ignition transformer leads are not
properly connected.
4 Ignition transformer is faulty.
5 The electrode faces are not at the right
distance.
6 Electrodes discharge to earth becau
-
se they are dirty or their insulation
is cracked: check also the porcelain
insulator terminals.
1 Pump pressure is not regular.
2 Water in the fuel.
3 Too much combustion air.
4 Air passage between flame disk and
diffuser excessively closed.
5 Nozzle worn out or dirty.
1 Thermostats (boiler or room) or pressu
-
re switches are open.
2 Photoresistor in short circuit.
3 Absence of line voltage, main switch
open, meter switch tripped or absence
of line voltage.
4 Thermostat line not wired according to
diagram or open thermostats.
5 Equipment internal fault.
REMEDY
1 Clean or replace.
2 Check all the smoke ducts in the boiler
and in the chimney.
3 Replace the equipment.
4 Clean.
1 Check the entire circuit.
2 Replace.
3 Restore the connection.
4 Replace.
5 Return to the required position.
6 Clean and if necessary replace them.
1 Adjust.
2 Drain water from the tank using a sui-
table pump. Never use the burner pump
for this purpose.
3 Reduce combustion air.
4 Correct the position of the combustion
head adjusting device.
5 Clean or replace.
1 Raise the thermostats settings, or
wait that the contacts close for natural
decrease of temperature or pressure.
2 Replace it.
3 Activate switches or wait for power to
return.
4 Check the connections and thermosta-
ts.
5 Replace it.
26 / 34
0006160393_202104
ENGLISH
Summary of Contents for TBL 1000 ME
Page 2: ......
Page 30: ...SCHEMI ELETTRICI TBL 650ME 750ME 1000ME 28 34 0006160393_202104 ITALIANO ...
Page 31: ...TBL 650ME 750ME 1000ME 29 34 0006160393_202104 ITALIANO ...
Page 32: ...TBL 650ME 750ME 1000ME 30 34 0006160393_202104 ITALIANO ...
Page 33: ...TBL 650ME 750ME 1000ME 31 34 0006160393_202104 ITALIANO ...
Page 34: ...TBL 650ME 750ME 1000ME I1 I2 BA I4 I3 32 34 0006160393_202104 ITALIANO ...
Page 36: ...34 34 0006160393_202104 ITALIANO ...
Page 64: ...WIRING DIAGRAMS TBL 650ME 750ME 1000ME 28 34 0006160393_202104 ENGLISH ...
Page 65: ...TBL 650ME 750ME 1000ME 29 34 0006160393_202104 ENGLISH ...
Page 66: ...TBL 650ME 750ME 1000ME 30 34 0006160393_202104 ENGLISH ...
Page 67: ...TBL 650ME 750ME 1000ME 31 34 0006160393_202104 ENGLISH ...
Page 68: ...TBL 650ME 750ME 1000ME I1 I2 BA I4 I3 32 34 0006160393_202104 ENGLISH ...
Page 70: ...34 34 0006160393_202104 ENGLISH ...
Page 71: ......