TECHNICAL SPECIFICATIONS
MODEL
TBG 80 SLX ME
TBG 100 SLX ME
TBG 160 SLX ME
Maximum natural gas heat power
kW
900
1400
2020
Minimum natural gas heat power
kW
165
175
230
¹) natural gas emissions
mg/kWh
Class 4
Class 4
Class 4
Operation
Electronic modulation
Electronic modulation
Electronic modulation
50 Hz natural gas transformer
26 kV 40 mA - 230 V
26 kV 40 mA - 230 V
26 kV 40 mA - 230 V
Methane maximum flow rate
Stm³/h
95
148
214
Methane minimum flow rate
Stm³/h
17
19
24
Maximum natural gas pressure
hPa (mbar)
200
200
200
Minimum natural gas pressure
hPa (mbar)
56
82
123
Maximum propane thermal power
kW
900
1330
1980
Minimum propane thermal power
kW
165
200
300
Propane maximum flow rate
Stm³/h
37
54
81
Propane minimum flow rate
Stm³/h
7
8
12
Maximum propane pressure
hPa (mbar)
200
200
200
Minimum propane pressure
hPa (mbar)
49
90
89
²)propane emissions
mg/kWh
Class 4
Class 4
Class 4
50hz fan motor
kW
1.5
2.2
3
50Hz three-phase electrical data
3L - 400V - 3.1A - 1.76kW 3L - 400V - 4.6A - 2.46kW 3L - 400V - 6.3A - 3.49kW
50Hz single-phase electrical data
1N - 230V - 0.50A -
0.114kW
1N - 230V - 0.50A -
0.114kW
1N - 230V - 0.50A -
0.114kW
Protection rating
IP40
IP40
IP40
Flame detection
IONISATION PROBE
IONISATION PROBE
IONISATION PROBE
Control box
BT 330
BT 330
BT 330
Air flow rate regulation
ELECTRONIC CAM
ELECTRONIC CAM
ELECTRONIC CAM
Operating ambient air temperature
°C
-15 ÷ +40
-15 ÷ +40
-15 ÷ +40
Sound pressure**
dBA
74
75
78.7
Sound power***
dBA
87
88
91.8
Weight with packaging
kg
98.5
103
106
Weight without packaging
kg
64.8
69.2
74.8
Calorific power below reference conditions 15° C, 1013 hPa (mbar):
Natural gas: Hi = 9,45 kWh/Stm³ = 34,02 MJ/Stm³
Propane: Hi = 24,44 kWh/Stm³ = 88,00 MJ/Stm³
For different types of gases and pressure values, contact our sales departments.
Minimum gas pressure, depending on the type of gas train used for obtaining max. flow rate with null pressure in the combustion chamber.
The measurements have been carried out in accordance with EN 15036 - 1 standard.
** The acoustic pressure measured with burner operating at maximum rated thermal output refers to the manufacturer's laboratory environment
conditions and cannot be compared to measurements carried out in different locations. Measurement accuracy σ = +/- 1.5 dB(A).
*** Acoustic pressure was obtained characterizing the manufacturer's laboratory with a sample source; this measurement has a class 2
accuracy (engineering class) with a standard deviation of 1.5 dB(A).
STANDARD ACCESSORIES
MODEL
TBG 80 SLX ME
TBG 100 SLX ME
TBG 160 SLX ME
Burner coupling flange gasket
1
1
1
Plenum chamber gasket
1
1
1
OR seal
1
1
1
Stud bolts
No. 8 M 12
No. 8 M 12
No. 8 M 12
Hexagon nuts
No. 12 - M12 / No. 4 - M6
No. 12 - M12 / No. 4 - M6
No. 12 - M12 / No. 4 - M6
Flat washers
No. 4 - Ø12 / No. 8 - Ø13
No. 4 - Ø12 / No. 8 - Ø13
No. 4 - Ø12 / No. 8 - Ø13
Toothed washers
No. 4 - M6 / No. 4 - M10
No. 4 - M6 / No. 4 - M10
No. 4 - M6 / No. 4 - M10
Screws
No. 4 - TE M10
No. 4 - TE M10
No. 4 - TE M10
7-pole connector
1
1
1
Gas train gasket
1
1
1
6 / 38
0006160424_202208
ENGLISH
Summary of Contents for TBG 80 SLX ME
Page 2: ......
Page 36: ...SCHEMI ELETTRICI TBG 80 SLX ME TBG 100 SLX ME TBG 160 SLX ME 34 38 0006160424_202208 ITALIANO...
Page 37: ...TBG 80 SLX ME TBG 100 SLX ME TBG 160 SLX ME 35 38 0006160424_202208 ITALIANO...
Page 38: ...TBG 80 SLX ME TBG 100 SLX ME TBG 160 SLX ME I1 I2 BA I4 I3 36 38 0006160424_202208 ITALIANO...
Page 40: ...38 38 0006160424_202208 ITALIANO...
Page 74: ...WIRING DIAGRAMS TBG 80 SLX ME TBG 100 SLX ME TBG 160 SLX ME 34 38 0006160424_202208 ENGLISH...
Page 75: ...TBG 80 SLX ME TBG 100 SLX ME TBG 160 SLX ME 35 38 0006160424_202208 ENGLISH...
Page 76: ...TBG 80 SLX ME TBG 100 SLX ME TBG 160 SLX ME I1 I2 BA I4 I3 36 38 0006160424_202208 ENGLISH...
Page 78: ...38 38 0006160424_202208 ENGLISH...
Page 79: ......