CAUTION / WARNING
The housings for the cables for the 7 and 4-pole plugs are
provided respectively for cable Ø 9.5÷10 mm and Ø 8.5÷9
mm, this ensures the protection rating is IP 44 (Standard IEC
EN60529) for the electrical panel.
Screw the screws (1) with adequate torque to ensure a correct seal to
reclose the electrical panel lid.
CAUTION / WARNING
Only professionally qualified personnel is allowed to open the
burner electrical panel.
• In case of unbalanced 230V phase-phase mains supply systems,
the voltage between the flame detector electrode and earth might
not be enough to ensure the correct operation of the burner. The
problem is eliminated using the isolation transformer type AR1
code 0005020028 which must be connected as shown in the
following diagram.
The electric motor is equipped with thermal protector with automatic
reset that stops the unit in case of overheating.
CAUTION / WARNING
In case of lock out it is necessary to check that the motor is not
faulty and search for the possible causes of its heating.