ELECTRICAL CONNECTIONS
•
It is advisable to make all connections with flexible electric wire.
•
Conductor minimum section must be 1.5 mm².
•
Electrical lines must be kept away from hot parts.
•
The burner installation is allowed only in environments with
pollution degree 2 as indicated in annex M of the EN 60335-
1:2008-07 regulation.
•
Make sure that the electric line to which the unit will be connected
has frequency and voltage ratings suitable for the burner.
•
The three-phase or single-phase power supply line must have
a switch with fuses. The standards also require a switch on the
burner's power line located outside the boiler room where it can
be accessed easily.
•
The main line, the relevant switch with fuses and the possible
limiter must be suitable to support the maximum current
absorbed by the burner.
•
The mains supply connection requires an omnipolar switch
with a contact opening gap equal to or greater than 3 mm in
accordance with current safety regulations.
•
Refer to the wiring diagram for electrical connections (line and
thermostats).
•
Unsheathe the external insulating cover of the power cable to
the necessary extent for the connection, thus avoiding the wire
from coming into contact with metal parts.
CAUTION / WARNING
Only professionally qualified personnel may open the
burner electrical switchboard.
•
In case of unbalanced 230V phase-phase mains supply
systems, the voltage between the flame detector electrode and
earth might not be enough to ensure the correct operation of the
burner. The problem is eliminated using the isolation transformer
type AR1 code 0005020028 which must be connected as shown
in the following diagram.
Ph
Ph 230
ION IN
ION PROBE
AR 1
ION
L (1)
IN (2)
tensione_elettrodi
Summary of Contents for TBG 2000 ME
Page 2: ......
Page 24: ...ITALIANO 22 26 0006160227_201702 SCHEMI ELETTRICI TBG 480 2000 ME ...
Page 25: ...ITALIANO 23 26 0006160227_201702 TBG 480 2000 ME ...
Page 26: ...ITALIANO 24 26 0006160227_201702 TBG 480 2000 ME ...
Page 27: ...ITALIANO 25 26 0006160227_201702 TBG 480 2000 ME ...
Page 50: ...ENGLISH 22 26 0006160227_201702 WIRING DIAGRAMS TBG 480 2000 ME ...
Page 51: ...ENGLISH 23 26 0006160227_201702 TBG 480 2000 ME ...
Page 52: ...ENGLISH 24 26 0006160227_201702 TBG 480 2000 ME ...
Page 53: ...ENGLISH 25 26 0006160227_201702 TBG 480 2000 ME ...
Page 55: ......