16 / 18
0006081547_201210
ENGLISH
• Only set the maximum temperature.
• Press Enter
!
To access and set the climatic external probe follow the steps
of chapter "ACCESS TO THE ADJUSTMENT FUNCTIONS".
• Select with
• Press Enter
ACCESS TO THE EXTERNAL SIGNAL FUNCTION (4-20 mA, 0-10 DPS POTENTIOMETER)
• Select with
,
• Press Enter
• Set data as indicated on the table,
Hot Water Installations
S t e a m B o i l e r
Installations
P term
200
120
600
I term
600
60
300
D term
200
60
25
Adjustment time
15
15
20
• Press Enter
to confirm.
• Press Exit
three times to return to the main screen.
• Select
and set P40 = 1
• Press Exit