12 / 18
0006081547_201210
ENGLISH
• Select with
,
• Press Enter
• Set data as indicated on the table,
Hot Water Installations Steam Boiler
Installations
P term
200
120
600
I term
600
60
300
D term
200
60
25
Adjustment time
15
15
20
• Press Enter
to confirm.
• Press Exit
three times to return to the main screen.
!
To access and set the pressure follow the steps of chapter
"ACCESS TO THE ADJUSTMENT FUNCTIONS".
• Select with
• Use
to move to the set pints to change the following
parameters,
- SWITCHING OFF (SET POINT + VALUE)
- COMMAND AT THE MINIMUM SETTING (SET POINT + VALUE)
- BOILER SET POINT
- SWITCHING ON (SET POINT - VALUE)
• Press Enter
to store the parameters.
• Press Exit
ACCESS TO THE PRESSURE ADJUSTMENT FUNCTION