ENGLISH
24 / 36
0006160064_201510
DETAIL OF THE MODULATION CONTROL
MOTOR SQM 40 FOR CAM ADJUSTMENT
1
2
3
4
0002938080
I MAXIMUM AIR OPENING (130°)
II TOTAL AIR CLOSURE (BURNER STOPPED)( 0°)
III IGNITION AIR OPENING (GREATER THAN CAM)
IV__TAB__MINIMUM AIR OPENING (LOWER THAN CAM III)
(15°)
1 Lever for enabling/disabling motor-camshaft coupling
2 Reference scale
3 Camshaft
4 Adjustable camshaft
Use the corresponding rings to modify the adjustment of the utili-
zed cams (I - II - III). The pointer on the red ring indicates the ro-
tation angle set for each cam on the respective reference scale.
SQN72.4C4A20 AIR SERVOMOTOR ADJUSTMENT
I 2nd flame air regulation cam (120°)
II Total air closure (burner stopped) (0°)
III 1st flame air regulation cam (10°)
IV Ignition air cam (30°) IV > III
V Ignition transformer cam (40°)*
* Cam V > IV (Approx. 5 - 10°)
1 Camshaft-motor coupling insertion and exclusion pin.
2 Reference scale
3 Position indicator
4 Adjustable camshaft
To adjust the setting of the cams used, use the corresponding
rings (I - II - III). The scale on the ring indicates the reference
scale of the rotation angle set for each cam.
Summary of Contents for GI 500 MC
Page 2: ......
Page 34: ...ITALIANO 32 36 0006160064_201510 SCHEMI ELETTRICI ...
Page 35: ...ITALIANO 33 36 0006160064_201510 ...
Page 36: ...ITALIANO 34 36 0006160064_201510 ...
Page 38: ...ITALIANO 36 36 0006160064_201510 ...
Page 70: ...ENGLISH 32 36 0006160064_201510 WIRING DIAGRAMS ...
Page 71: ...ENGLISH 33 36 0006160064_201510 ...
Page 72: ...ENGLISH 34 36 0006160064_201510 ...
Page 74: ...ENGLISH 36 36 0006160064_201510 ...
Page 75: ......