CONNECTRON “LKS 120-02 (B5-5-51) AIR DUMPER CONTROL SERVOMOTOR
AIR DAMPER CLOSED WHEN BURNER NOT OPERATING.
1) 2nd flame valve activation cam (black) must be in
an intermediate position between cams that regulate
the 1st and 2nd flame air
2) 1st flame air regulation cam (light blue)
3) 2nd flame air regulation cam (red)
4) Air damper in open position
5) Air damper in closed position
6) Button for 2nd flame manual control
7) Rotation direction inversion relay
8) Servomotor index reference.
1 Neutral
2 Phase
3 2nd flame thermostat
4/5 Micro switch for 2nd flame valve
ADJUSTMENT FOR SERVOMOTOR FIRST IGNITION
For the first ignition, adjust the cams preliminarily as
follows:
1) 2nd flame valve activation cam (black) 40°
2) 1st flame air regulation cam (light blue) 25°
3) 2nd flame air regulation cam (red) 50°
4) Light blue
5) Black
6) Red
CAUTION / WARNING
The cam position must be adjusted to the ef
-
fective fuel output, verifying the combustion
with specific instruments.
Air flow rate in the 1st flame position must cor
-
respond to at least 50% of the total air flow.
ENGLISH
19 / 30
0006080763_201611