Special instructions for using gas.
•
Check that the feed line and the train comply with current stan
-
dards and regulations.
•
Check that all the gas connections are properly sealed.
•
Do not leave the equipment on when it is not in use and always
close the gas cock.
•
If the user is away for some time, close the main gas feed valve
to the burner.
•
If you smell gas:
-
do not operate electrical switches, the phone or any other
object that can cause sparks;
-
immediately open doors and windows to create a draught to
clear the air in the room;
- close the gas cocks;
-
have professionally qualified personnel correct the fault.
•
Do not block ventilation openings in the room where there is gas
equipment or dangerous situations may arise with the build up
of toxic and explosive mixtures.
RESIDUAL RISKS
• In spite of the accurate product planning according to the regu-
lations in force, residual risks may still be present during correct
use. They are indicated on the burner by means of specific Pi
-
ctograms.
CAUTION
Mechanical parts in motion.
CAUTION
Materials at high temperatures.
CAUTION
Energised electrical switchboard
INSTRUCTIONS ON ELECTRICAL SAFETY
•
Check that the equipment is properly grounded according to the
safety standards in force.
•
Do not use the gas pipes to ground electrical equipment.
•
If in doubt, call for a careful electrical check by a qualified tech
-
nician, since the manufacturer will not be liable for any damage
caused by a poor ground connection.
•
A professional check should be carried out to ensure that the
electrical installation is adequate for the maximum output ab
-
sorbed by the system. This is indicated on the data plate.
•
Make sure that the system cable cross-section is suitable for
the power absorbed by the equipment.
• The use of adaptors, multiple plugs and/or extension leads to
supply power from the mains to the appliance is not allowed.
•
For the connection to the mains, fit an omnipolar switch with a
contact opening gap equal to or greater than 3 mm in accor
-
dance with current safety regulations (Overvoltage category III).
•
Use only double insulated cables with external thickness of at
least 1mm for the power supply of the burner.
•
Unsheathe the external insulating cover of the power cable to
the necessary extent for the connection, thus avoiding the wire
from coming into contact with metal parts.
•
The electrical supply to the burner must have neutral to ground
connection. In the case of a ionisation current check with neu-
tral not to ground, it is essential to make a connection between
terminal 2 (neutral) and the ground for the RC circuit.
•
If the user is away for some time, close the main gas feed valve
to the burner.
•
The use of any components that use electricity means that cer
-
tain fundamental rules have to followed, including the following:
-
do not touch the equipment with parts of the body that are
wet or damp and/or with damp feet
-
do not pull on electrical cables;
-
do not leave the equipment exposed to atmospheric agents
(such as rain or sun etc.) unless there is express provision
for this.
-
do not allow the equipment to be used by children or inexpe
-
rienced persons.
-
The power supply cable for the equipment not must be
replaced by the user. If the cable is damaged, turn off the
equipment. To replace the cable, contact exclusively quali
-
fied personnel.
-
If you decide not to use the equipment for a while it is advi
-
sable to switch off the electrical power supply to all compo
-
nents in the system that use electricity (pumps, burner, etc.).