CONVERSION FROM NATURAL GAS TO LPG
To fit the nozzle, proceed as follows:
• close the gas valve;
• disconnect the gas valve (b) from the mixer unit (c) loosening
the four fastening screws;
•
fit the nozzle for fuel GPL (d) inside the gasket (e);
• assemble the components, making sure to correctly position the
sealing gaskets (e)
• switch on the appliance once assembling is complete.
Upon ignition, carry out a leak test of the gas circuit and make sure
that oxygen values (O2%) at max. and min. power are within the
tolerances shown in the table below.
CAUTION
Once the conversion has been carried out, apply the
supplied adhesive plate "GPL" (h) on the burner.
Set the value of O2 and rpm of the fan as shown in the table.
Burner model input
range kW
Fuel
Fan rpm
Nozzle diameter
O2% value
Minimum thermal
capacity
Maximum thermal
capacity
Minimum thermal
capacity
Maximum thermal
capacity
BPM 90E 20-85kW
G20 methane
1650
6800
NO
5.5 ± 0.5
5.0 ± 0.5
G31 Propane
1650
6000
6.75 mm
6.0 ± 0.5
4.8 ± 0.3
BPM 90E 20-75kW
G20 methane
1650
6000
NO
5.5 ± 0.5
5.0 ± 0.5
G31 Propane
1650
5400
6.75 mm
6.0 ± 0.5
4.8 ± 0.3
BPM 90 E 20-50
kW
G20 methane
1650
4000
NO
5.5 ± 0.5
5.0 ± 0.5
G31 Propane
1650
3600
6.75 mm
6.0 ± 0.5
4.8 ± 0.5
BPM 140 E
G20 methane
1650
6800
10.7 mm
5.5 ± 0.5
4.5 ± 0.5
G30 butane
-
-
-
-
-
G31 Propane
-
-
-
-
-