22 / 30
0006081265_201212
ENGLISH
0x1C
●
ERROR_SYNCHRONISATION_DURING_
INITIALISATION
0x1D
●
ERROR_PROCESSOR MALFUNCTION
? The MPA is subject to strong EMC interferences
0x1E
●
ERROR_STATE BLOCK_SFR REGISTER
...
Free
10.3 Errors in the expansion functions (from 0x40 to 0x9F)
0x40
ERROR_FAN RATED VALUE PRESETTING
? In the curve segment a fan rated value has been preset that
is lower than the minimum rpm value or higher than the fan
maximum rpm value (P26 or P27). For example: P26 (minimum
rmp value) could be set to 500 rpm, while the number of revs for
the modulation degree is pre-set to 480 rpm. Or P27 (maximum
rpm value) is set to 5600 rpm, while pre-ventilation B has to be
performed at 5800 rpm.
0x41
ERROR_FAN_DEVIATION
? The number of pulses of the fan response is improperly set
? The fan is not suitable for the required number of revs
? The pre-set tolerance is too low or the fan regulator is not
optimised
0x42
ERROR_FAN_NO_RESPONSE
? The fan response line has not been connected properly or
it is interrupted
? The fan is blocked and does not turn
? The fan receives no current or it is faulty
0x43
ERROR_IONISATION INPUT_TEST
0x44
ERROR_CURVE CRC16_TEST
? The curve segment has been temporarily modified (for ex. for
the first commissioning), but then it has been properly enabled
0x45
●
E R R O R _ M O D U L A T I O N D E G R E E
PRESETTING_NOT VALID
0x46
Free
0x47
●
ERROR_STEP MOTOR TYPE_NOT VALID
0x48
ERROR_TOLERANCE ExCEEDED_STEP
MOTOR
? The cables to the step motor are not properly connected or
are partly interrupted
? The step motor has a torque that is higher than the one
permitted, for example due to an improper installation of the
cover or to pressure drops.
0x49
ERROR_REFERENCE NOT FOUND_STEP
MOTOR
? see error 0x48
0x4A
ERROR_NO_REACTION_STEP MOTOR
? see error 0x48
0x4B
ERROR_PARAMETERS SET STICK_NOT
FOUND
? Parameters set activated but not entered into the MPA
? Faulty stick
? The duration of the adjustment operation (P70) takes more
than 23 h and 59 min and continuous operation has not been
activated
? The PWM output have been set to analog operation (0..10 V
or 4...20 mA), but the appropriate stick has not been inserted.
0x4C
ERROR_PARAMETERS SET STICK_
ALIGNMENT BLOCK
? A parameter could not be transferred from the stick, for
example because the MPA variables limits have been reduced
0x4D
ERROR_PARAMETERS SET STICK_WRONG
PASSWORD
? The entered password is not valid for this stick
0x4E
ERROR_PARAMETERS SET STICK_NO_
CONTINUOUS OPERATION
? The duration of the adjustment operation (P70) takes more
than 23 h and 59 min and continuous operation has not been
activated
0x4F
ERROR_PARAMETERS SET STICK_STICK_
TYPE
? The stick is not suitable for this type of automatic device
0x50
●
ERROR_WRONG_SUPPL V_RESPONSE
0x51
ERROR_SUPPL V_DELAY_NOT VALID
? The parameters P25 or P53 have been set to a non permitted
value, since the status (P50 or P51) cannot last so long
0x52
Free
0x53
ERROR_LACK OF GAS_GDWVPS
0x54
●
ERROR_PWM_CALIBRATION VALUES
? During the programming of the parameters set stick, the
EEPROM has been modified or deleted
? Parameters set stick faulty
Summary of Contents for BPM 140 EVO
Page 2: ......
Page 27: ...27 30 0006081265_201212 ITALIANO SCHEMI ELETTRICI...
Page 29: ...29 30 0006081265_201212 ITALIANO...
Page 48: ...20 30 0006081265_201212 ENGLISH...
Page 55: ...27 30 0006081265_201212 ENGLISH WIRING DIAGRAMS...
Page 57: ...29 30 0006081265_201212 ENGLISH...
Page 83: ...27 30 0006081265_201212 DEUTSCH SCHALTPLAN...
Page 85: ...29 30 0006081265_201212 DEUTSCH...
Page 111: ...27 30 0006081265_201212 P O L S K I SCHEMATY ELEKTRYCZNE...
Page 113: ...29 30 0006081265_201212 P O L S K I...
Page 115: ......