17 / 30
0006081265_201212
ENGLISH
Connection diagram for expansion modules with type A attachments:
variable
standard
Step motor
Analog IN/OUT
Display
TWI
Sensor B Sensor
A
Command B
Command
A
DGND +24 V
DGND 10 V IN Shunt 20 mA
IN
+24 V 10 V OUT 20 mA
OUT
(minus)
20 mA
OUT
(plus)
+24 V
DGND Date RESET DIR CLK
+5 V DGND SCA
SCL
FUNCTION LIST
MPA 5111
Supplementary valve
●
230 V Remote reset
●
Internal fuse
●
Flame control feed (ION_PWR), for KLC xxxx
●
GDWVPS input
●
Internal 24V transformer for step motor
●
7 BEHAVIOUR DESCRIPTION
7.1 Reset function
Pressing the reset key in the lock-out status (status 0) the MPA can
be reset. The key has to be held down for at least ¼ of a second to
distinguish the action from any EMC pulse disturbances. The same
is valid for 230 V reset.
According to Standard DIN EN 14459 (appendix J), the number of
possible resets is limited to 5 in 15 minutes. This means that after 5
resets performed in short time intervals the automatic device does
not allow further resets. The MPA can be reset again after a waiting
time during which the MPA is supplied by power.
The waiting time is 15 minutes or 3 minutes per reset.
Prolonged reset
The above described limit of 5 resets in 15 minutes can be cleared
using the "prolonged reset".
In this case the reset button should be pressed for at least 5 seconds
(10 seconds max) (the display starts flashing after 5 seconds).
The "prolonged reset" is active in all MPA operating statuses,
therefore using the "prolonged reset", you could have the MPA
perform a safety deactivation with restart e.g. during operation with
presence of flame.
The prolonged reset is not possible via the 230V reset input.
Summary of Contents for BPM 140 EVO
Page 2: ......
Page 27: ...27 30 0006081265_201212 ITALIANO SCHEMI ELETTRICI...
Page 29: ...29 30 0006081265_201212 ITALIANO...
Page 48: ...20 30 0006081265_201212 ENGLISH...
Page 55: ...27 30 0006081265_201212 ENGLISH WIRING DIAGRAMS...
Page 57: ...29 30 0006081265_201212 ENGLISH...
Page 83: ...27 30 0006081265_201212 DEUTSCH SCHALTPLAN...
Page 85: ...29 30 0006081265_201212 DEUTSCH...
Page 111: ...27 30 0006081265_201212 P O L S K I SCHEMATY ELEKTRYCZNE...
Page 113: ...29 30 0006081265_201212 P O L S K I...
Page 115: ......