SPECIAL PRECAUTIONS WHEN USING GAS.
• Check that the feed line and the train comply with current law and
regulations.
• Check that all the gas connections are properly sealed.
• Do not leave the equipment on when it is not in use and always close
the gas cock.
•
If the user is absent for a prolonged period of time, close the main
gas feed tap to the burner.
• If you smell gas:
-
do not operate electrical switches, phones or any other object
that may cause sparks;
- open immediately doors and windows to create a draught to
clear the air in the room;
- close the gas cocks;
-
have professionally qualified personnel correct the fault.
•
Do not obstruct ventilation openings in the room where there is gas
equipment. Otherwise, dangerous situations may arise with the build
up of toxic and explosive mixtures.
•
If the user is absent for a prolonged period of time, close the main
gas feed tap to the burner.
RESIDUAL RISKS
•
Even though the product was designed in compliance with the obli
-
gatory standards, residual risks may still be present during correct
operation. They are signalled on the burner through special Picto
-
grams.
CAUTION
Moving mechanical organs.
CAUTION
Materials at high temperature.
CAUTION
Powered electric panel.
ELECTRIC SAFETY WARNINGS
•
Check that the equipment has a suitable ground system, carried out
following safety standards in force.
•
Have qualified personnel check that the electric system is adequate
to equipment maximum power consumption indicated on the plate.
• For the mains supply connection is required an omnipolar switch
with a contact opening gap equal or above 3 mm in accordance with
current safety regulations (condition of overvoltage category III).
•
Remove the external insulating seal of the supply pipe necessary for
the connection, preventing the cable to touch metal parts.
• The use of any electrically fed components entails complying with
certain fundamental rules, including the following:
-
do not touch the equipment with parts of the body that are wet or
damp or with damp feet;
-
do not pull on electrical cables;
-
do not leave the equipment exposed to atmospheric agents
(such as rain or sun etc.) unless there is explicit provision for
this;
-
do not allow the equipment to be used by children or inexpert
persons;
-
The power supply cable for the equipment must not be replaced
by the user. In case of cable damage, turn the equipment off. To
replace it contact qualified personnel only;
- If you decide not to use the equipment for a certain period of time
it is advisable to switch off the electrical power supply to all com
-
ponents in the system that use electricity (pumps, burner, etc.).
•
Use regulation-compliant flexible cables EN60335-1:EN 60204-1
- in case of PVC sheath, at least type H05VV-F;
-
in case of rubber sheath, at least type H05RR-F; LiYCY
450/750V
- without any sheath, at least type FG7 o FROR, FG70H2R
• The electric equipment works correctly at altitudes of up to 1000 m
above the see level.
TO BE CARRIED OUT BY THE INSTALLER
•
Install a suitable circuit breaker for each power supply line of the bur
-
ner, according to the characteristics and the diagram on the chapter
ELECTRICAL CONNECTIONS.
•
The disconnection must be carried out by means of a device com
-
plying with the following requirements:
-
A disconnecting switch - circuit breaker, according to IEC 60947-
3 for at least the equipment category AC-23 B (non-frequent
operations on highly inductive loads or AC motors).
-
A control and protection switching device suitable for isolation
according to IEC 60947-6-2.
-
A switch suitable for isolation according to IEC 60947-2.
• The disconnecting device must:
- Ensure the isolation of the electrical equipment from the power
supply line when in the stable OFF position indicated with “0”,
and be in a stable ON position indicated with “1”.
-
Feature a visible gap between contacts or a position indicator
that cannot indicate OFF (isolated) until all contacts are actually
open and the requirements for the isolation function are met.
-
Feature a grey or black actuator which can be easily identified.
-
Be padlockable in the OFF position. In case of lock-out, remote
and local activation will not be possible.
- Disconnect all the active conductors of its power supply circuit.
For TN power supply systems, the neutral conductor can be
disconnected or not, except in the countries where the discon
-
nection of the neutral conductor (if used) is mandatory.
•
Both disconnecting controls must be located at a height between 0,6
m ÷ 1, 7 m with respect to the working plane.
•
Since circuit breakers are not emergency devices, they can feature
an additional cover or a door, which can be easily opened without
any key or tool. Its function must be clearly indicated, e.g. with the
relevant symbols.
•
The burner can be installed only in TN or TT systems. It cannot be
installed in isolated system of IT type.
ENGLISH
4 / 46
0006160271_202007
Summary of Contents for 18190010
Page 2: ......
Page 38: ...SCHEMI ELETTRICI ITALIANO 36 46 0006160271_202007 ...
Page 39: ...ITALIANO 37 46 0006160271_202007 ...
Page 40: ...ITALIANO 38 46 0006160271_202007 ...
Page 41: ...ITALIANO 39 46 0006160271_202007 ...
Page 42: ...ITALIANO 40 46 0006160271_202007 ...
Page 43: ...ITALIANO 41 46 0006160271_202007 ...
Page 44: ...ITALIANO 42 46 0006160271_202007 ...
Page 45: ...ITALIANO 43 46 0006160271_202007 ...
Page 46: ...ITALIANO 44 46 0006160271_202007 ...
Page 47: ...ITALIANO 45 46 0006160271_202007 ...
Page 84: ...WIRING DIAGRAMS ENGLISH 36 46 0006160271_202007 ...
Page 85: ...ENGLISH 37 46 0006160271_202007 ...
Page 86: ...ENGLISH 38 46 0006160271_202007 ...
Page 87: ...ENGLISH 39 46 0006160271_202007 ...
Page 88: ...ENGLISH 40 46 0006160271_202007 ...
Page 89: ...ENGLISH 41 46 0006160271_202007 ...
Page 90: ...ENGLISH 42 46 0006160271_202007 ...
Page 91: ...ENGLISH 43 46 0006160271_202007 ...
Page 92: ...ENGLISH 44 46 0006160271_202007 ...
Page 93: ...ENGLISH 45 46 0006160271_202007 ...
Page 95: ......