FIXING THE BURNER TO THE BOILER
The burner must be applied to the boiler iron plate after having fixed the supplied stud bolts according to the drill
-
ing template. It is advisable to electrically weld the stud bolts inside the plate so as to prevent them from being
extracted jointly with the burner check nuts if the burner is dismantled.
To insert the insulating flange, which must be placed between the burner and the boiler plate, dismantle the end
part of the combustion head. To connect the burner to the boiler, the special nuts and relevant washers are sup
-
plied with the burner. The burner is equipped with cylindrical combustion head; it is advisable to first fix the boiler
plate, and then the burner. An insulating protection having a minimum thickness of 10 mm must be placed between
plate and boiler when the boiler port is not provided with thermal insulation.
The boiler plate must be designed according to our drawings, with a minimum thickness of 10 mm. so as to prevent
possible deformations. Before applying the burner to the boiler, the sliding flange must be arranged so as to allow
the burner head to penetrate in the combustion chamber by the amount required by the manufacturer.
Once this operation has been finished, connect the burner to the gas pipes as explained in the following pages,
based on the available type of gas supply (low pressure or mean pressure).
Pressure transmission pipe in combustion chamber
Burner flange
Pressure detection pipe
connection nipple in combustion chamber
Pressure take-off in combustion chamber
MEASURING THE PRESSURE IN THE COMBUSTION CHAMBER
If the hole in the door is too small to allow the hose to pass and the door has no flame inspection window it will be
necessary to make a Ø 12 hole at the site of the 1/4” connection for the insertion of the pressure take up hose in
the combustion chamber (provided with the burner)
Plate
and
refractory
wall
hole
to
be
drilled
to
Ø
12
ENGLISH
PRESSURE AND POSITION DETECTOR
N° 0002934090
Rev.20/01/2004
Summary of Contents for 15360010
Page 94: ...94 107 0006080870_200709 Coffrets de s curit pour br leurs gaz LFL 1 N 7451 REV 07 1996...
Page 95: ...95 107 0006080870_200709...
Page 96: ...96 107 0006080870_200709...
Page 97: ...97 107 0006080870_200709...
Page 98: ...98 107 0006080870_200709...
Page 99: ...99 107 0006080870_200709...
Page 103: ...103 107 0006080870_200709...
Page 104: ...104 107 0006080870_200709...
Page 105: ...105 107 0006080870_200709...
Page 106: ...106 107 0006080870_200709...
Page 107: ...107 107 0006080870_200709...