Process data (continued)
Counter Reset
1
Reset counter value to zero.
LED Off
1
Emitter and object detection inactive.
The sensor assumes the following state:
Function
Status
BDC1
0
Pin 2 (SIO)
High-resistance
Pin 4 (SIO)
High-resistance
Counter reading
Remains unchanged
Stability
0
Factory setting
Additional functions are disabled as default or with system
command
Restore factory settings
(value 0x82)
deactivated.
The following settings are available:
Parameters
Factory
setting
Comment
Sensor Principle
0
Diffuse energetic
sensor
SIO Output Type
1
PNP
Device Access Locks
0
All functions
enabled
Application Specific Tag
„“
Switchpoint Mode
1
Singlepoint Mode
Switchpoint Logic Pin 4
0
Normally open
(NO)
Debounce Time Pin 2
0
Inactive
Config Pin 2
0
Switching output,
normally closed
(NC)
Switchpoint Hysteresis
5
Setpoint SP1
4095
Setpoint SP2
4095
Counter function / frequency monitor
Mode
0
Inactive
Limit
1
StartupDelay
0
Inactive
UpperLimitHigh
5000
UpperLimitLow
4000
LowerLimitHigh
2000
LowerLimitLow
1000
Time functions
Delay Function Mode
0
Delay
Delay Time 1 (On delay)
0
Inactive
Delay Time 2
(Off delay, One shot)
0
Inactive
Factory default setting (continued)
Parameters
Factory
setting
Comment
Operating hours counter
Operating hours
maintenance
0
Smart sensor functions
Fig. 5: Smart sensor functions
Switching outputs in SIO/IO-Link mode
SIO mode
In the factory default setting the digital outputs Q1 and Q2
are configured as PNP switching outputs. The switching
logic for Q1 is normally open, Q2 is normally closed.
The digital switching outputs can be configured via IO-Link
as PNP, NPN or push-pull output type (parameter 0x00B4).
The switching logic for Q1 can be configured via IO-Link
(parameter 0x003D) as normally open or normally closed.
The switching logic for Q2 is complementary to Q1.
IO-Link operation
Pin 4 is the communication channel (C). Pin 2 is always
high-resistance.
The switchpoint information for Q1 in SIO mode
corresponds to BDC1 in IO-Link mode. When toggling
between IO-Link and SIO mode the settings (switching
logic, switchpoints) remain unchanged.
When operating with NPN output on an IO-Link master
IO-Link communication is still possible, but in SIO mode
the switching state is not evaluated.
When the counting function is enabled other configurations
are possible for Pin 4 and Pin 2 in SIO mode (see Section