Balluff Network Interface / IO-Link BNI IOL-719-002-Z012
www.balluff.com
26
4
IO-Link Interface
Pt100/Pt1000
mode F3
hex
The measurement method for the Pt sensor can be set with this ISDU register.
Accessing the ISDU register through the subindex 0, the resolution for all ports can be
read/written. Accessing the ISDU register through subindex 1-8, the resolution for the
corresponding port (P0-P7) can be read/written,
0 = 2 wire measurement
1 = 3 wire measurement
2 = 4 wire measurement
Subindex 0:
Byte
0
1
2
3
4
5
6
7
P
t
mod
e
P
o
rt
0
P
t
mod
e
P
o
rt
1
P
t
mod
e
P
o
rt
2
P
t
mod
e
P
o
rt
3
P
t
mod
e
P
o
rt
4
Pt
mod
e
P
o
rt
5
P
t
mod
e
P
o
rt
6
P
t
mod
e
P
o
rt
7
Wire break
disable F4
hex
In case of Pt 100, Pt1000, Typ J, Typ K and Type C the BNI IOL-719-002-Z012-XXX can detect
wire break condition. In some cases with a calibrator unit, the wire break detection will be
activated. In order to be able to use calibrator to calibrate the module, the wire break detection
can be disabled.
It is recommended to enable the wire break detection during normal operation.
0 = Enabled
1 = Disabled
Process data
format F5
hex
The analog value can be represented in different formats in the process data.
0 = Signed
1 = Unsigned
2 = Dimensioned (mV, uA, x0.1 °C)
Summary of Contents for BNI IOL-719-002-Z012
Page 1: ...BNI IOL 719 002 Z012 english User s Guide deutsch Betriebsanleitung...
Page 2: ...www balluff com...
Page 3: ...BNI IOL 719 002 Z012 Bedienungsanleitung...
Page 37: ...BNI IOL 719 002 Z012 User s Guide...
Page 71: ...BNI IOL 719 002 Z012...
Page 104: ...IO Link BNI IOL 719 002 Z012 www balluff com 33...