Balluff Network Interface / IO-Link BNI IOL-719-002-Z012
www.balluff.com
6
3
Getting Started
3.2.
Mechanical
connection
The BNI IOL-719-002-Z012 modules are attached by using 2 M6 screws and
2 spacers.
3.3.
Electrical
connection
The BNI IOL-719-002-Z012 modules require no separate supply voltage connection. Power
is provided through the IO-Link interface by the host IO-Link Master.
IO-Link Interface
IO-Link (M12, A-coded, male)
Pin
Function
1
Power supply controller, +24V, max 1.1A
2
-
3
GND, reference potential
4
C/Q, IO-Link data transmission channel
Connecting the
Sensor Hub
➢
Connection protection ground to FE terminal, if present.
➢
Connect the incoming IO-Link line to the Sensor Hub.
Note
A standard 3 wire sensor cable is used for connection to the host IO-Link master
.
Function earth
Note
The FE connection from the housing to the machine must be low-impedance
and kept as short as possible.
Module versions
Sensor Hub Version
Analog function
BNI IOL-719-002-Z012
8 Analog input