www.balluff.com
13
3
Getting Started
Example 2:
The analog mode is set to 4-20 mA
The resolution is 12 bit.
The process data is left aligned.
The digitalized value read over IO-Link is ABC0
hex
In case of 4-20 mA, the analog input current range is between 3.8 mA and 20.5 mA. The
digitalized value is read over IO-Link as a 16 bit value, but the resolution is 12 bit and it is
left aligned, so the 12 bit digitalized data is ABC
hex
= 2748.
Input current [mA] = PortValue ∗
I
max
− I
min
2
N
− 1
+ 𝐼
𝑚𝑖𝑛
= 2748 ∗
20.5𝑚𝐴 − 3.8𝑚𝐴
2
12
− 1
+ 3.8𝑚𝐴 = 15.007𝑚𝐴
Example 3:
The analog mode is set to TypJ Thermocouple.
The resolution is 16 bit
The digitalized value read over IO-Link is 4567hex = 17767
Temperature [°C] = PortValue ∗
T
max
−T
min
2
N
−1
+ T
min
= 17767 ∗
1200°𝐶−(−100°𝐶)
2
16
−1
+ (−100°C) = 252.44 °𝐶