Balluff Network Interface / IO-Link BNI IOL-719-002-Z012
www.balluff.com
24
4
IO-Link Interface
Analog
mode F0
hex
The mode of the input ports can be set with this ISDU register.
Accessing the ISDU register through the subindex 0, the settings for all ports can be read/written.
Accessing the ISDU register through subindex 1-8, the port mode for the corresponding port
(P0-P7) can be read/written.
00
hex
= Voltage input, 0V - 10V
01
hex
= Current input, 4mA
– 20 mA
02
hex
= Voltage input, 5V
– 10V
03
hex
= Voltage input, -10V
– 10V
04
hex
= Voltage input, 0V
– 5V
05
hex
= Current input, 0mA
– 20 mA
06
hex
= Voltage input, -5V - +5V
07
hex
= Pt100
08
hex
= Pt1000
09
hex
= Type J thermocouple
0A
hex
= Type K thermocouple
0B
hex
= Type C thermocouple*
FF
hex
= Port is switched off
*available from FW3.0
Subindex 0:
Byte
0
1
2
3
4
5
6
7
Mod
e
P
o
rt
0
Mod
e
P
o
rt
1
Mod
e
P
o
rt
2
Mod
e
P
o
rt
3
Mod
e
P
o
rt
4
Mod
e
P
o
rt
5
Mod
e
P
o
rt
6
Mod
e
P
o
rt
7
Attention!
•
Changing the analog mode of the port to voltage or current input, +24V will be
switched between pin1 and pin3, in order to supply the analog sensor.
•
Please note that no temperature sensor (Pt100 or Pt1000) is connected to such
a port.
•
If a temperature sensor (Pt100 or Pt1000) is connected to an analog port that is
not configured as Pt100 or Pt1000, the following current can cause the sensor
to heat up and/or damage it. There may be a risk of burns.
Summary of Contents for BNI IOL-719-002-Z012
Page 1: ...BNI IOL 719 002 Z012 english User s Guide deutsch Betriebsanleitung...
Page 2: ...www balluff com...
Page 3: ...BNI IOL 719 002 Z012 Bedienungsanleitung...
Page 37: ...BNI IOL 719 002 Z012 User s Guide...
Page 71: ...BNI IOL 719 002 Z012...
Page 104: ...IO Link BNI IOL 719 002 Z012 www balluff com 33...