Page 25
IBVR20 software 8.43.doc
Issue 1
If an output between 1-10 is required for the assigned switch “a” then move the cursor
along until it flashes beneath that window and then enter 01.
If an output between 1-10 is required for the assigned switch “b” then move the cursor
along until it flashes beneath that window and then enter 02. If it has already been
assigned to “a” then the value 03 (a+b) must be entered.
For outputs 11-20 page down to the 4
th
page of BVRM zone positions and repeat as
above.
When using a combination of “a“, ”b” “c” and “d” refer to code table below to enter
correct code for output operation in 2
nd
and 4
th
page of BVRM zone positions.
00 = 0
08 = d
01 = a
09 = a+d
02 = b
10 = b+d
03 = a+b
11 = a+b+d
04 = c
12 = c+d
05 = a+c
13 = a+c+d
06 = b+c
14 = b+c+d
07 = a+b+c
15 = a+b+c+d
Example
------------------------------------------
| PORT 1 out|01|02|03|04|05|06|07|08|09|10 |
| a=07 b=11)|01|02|03|04|05|06|07|08|09|10 |
------------------------------------------
------------------------------------------
| PORT 1 out|01|02|03|04|05|06|07|08|09|10 |
| group mode|
01
|
02
|
04
|
08
|00|00|
03
|00|
12
|
08
|
------------------------------------------
------------------------------------------
| PORT 1 out|11|12|13|14|15|16|17|18|19|20 |
| c=09 d=10)|11|12|13|14|15|16|17|18|19|20 |
------------------------------------------
------------------------------------------
| PORT 1 out|11|12|13|14|15|16|17|18|19|20 |
| group mode|
07
|00|00|00|00|
15
|00|00|00|00 |
------------------------------------------
In above example : “ a ” = Switch 7 --- Operates outputs 1, 7, 11 & 16
“ b ” = Switch 11 --- Operates outputs 2, 7, 11 & 16
“ c ” = Switch 9 --- Operates outputs 3, 9, 11 & 16
“ d ” = Switch 10 --- Operates outputs 4, 9, 10 & 16
For values in bold refer to code table above.