Page 26
IBVR20 software 8.43.doc
Issue 1
16. Press the Page down key until the display steps to the 5
th
page of BVRM zone positions
Port 2 01-10.
------------------------------------------
| PORT 2 out|01|02|03|04|05|06|07|08|09|10 |
| a=00 b=00)|01|02|03|04|05|06|07|08|09|10 |
------------------------------------------
For Port 2 settings for BVRM refer to sections 9-14 above.
17. Press the Page down key until the display steps to the message length settings.
------------------------------------------
| MESSAGE |01|02|03|04|05|06|07|MES SYNC |
| time secs|00|00|00|00|00|00|00|mode 00 |
------------------------------------------
Note: The DIL switches mounted on the OPT402 for message 1 should be set for the
message length plus 5seconds. For messages 2 to 7 switches 1-7 should be on and
switch 8 should be off.
The message lengths are set as follows.
Move the cursor along until it flashes beneath the required message window.
If the length (seconds) required is between 0-9, enter it directly using the numbered
keys. Note the cursor automatically steps to the next message. Or using the + or – keys
will increase or decrease the value between 00 and 63 seconds.
When several BVR20 are used on 1 site it may be desirable to synchronize messages
to prevent an unwanted echo.
Synchronization is achieved by selecting 1 of the following modes:
00 No TX or RX
01 TX only
02 RX, message 1 only.
03 TX & RX, message 1 only.
04 RX, all messages.
05 TX & RX, all messages.
Note: When sync is required between dual messages 2 & 3, 4 & 5, 6 & 7 the message
time must be the same e.g. 2 must be the same as 3.
To change the mode, move the cursor along until it flashes beneath the message sync
window. Use keys 0-5 to select mode.
18. Press the Page down key again.
The display steps to the 1
st
page of fire panel interface mode settings, inputs 01-10.
------------------------------------------
| F/P input|01|02|03|04|05|06|07|08|09|10 |
| input mode|RS|00|00|00|00|00|00|00|00|00 |
------------------------------------------
↑
Note:
Fire panel input 1 is always the reset input normally open non latching mode
and can not be changed. When reset is applied there will be a 3 Second delay.