Page 28
IBVR20 software 8.43.doc
Issue 1
Message 12 = evac message 1, alert message 2.
Message 13 = evac message 1, alert message 3.
Message 14 = evac message 1, alert message 4.
Message 15 = evac message 1, alert message 5.
Message 10 = evac message 1, alert message 6.
Message 11 = evac message 1, alert message 7.
Message 8 = evac message 2, alert message 4.
Message 9 = evac message 2, alert message 6.
To change a message, move the cursor along until it flashes beneath the required
output 1-10 window. If the message required is between 0-9, enter it directly using the
numbered keys, or using the + or – keys step to the message number required between
00 and 15.
21. Press the Page down key again.
The display steps to the 2
nd
page of fire panel input 02 message start delay time
selection, outputs 1-10.
------------------------------------------
| F/P 02 out|01|02|03|04|05|06|07|08|09|10 |
| time 30sec|00|00|06|06|12|12|18|18|24|24 |
------------------------------------------
On receipt of an alarm condition from the fire detection system, the message broadcast
may be delayed to any output from 0 to 31.5 minutes, providing phased evacuation, a
requirement for high rise buildings.
In the example above, outputs 1 and 2 would be evacuated instantly, outputs 3 and 4
after 3 minutes, outputs 5 and 6 after 6 minutes and so on.
Important: If a delay is not required ensure time settings are set to 00.
To change a message start delay time, move the cursor along until it flashes beneath
the required output 1-10 window.
If the time required is between 0-9, enter it directly using the numbered keys, or using
the + or – keys step to the time in increments of 30 seconds, value between 00 and 63.
22. Press the Page down key again.
The display steps to the 3
rd
page of fire panel input 02 message selection, outputs 11-
20.
------------------------------------------
| F/P 02 out|11|12|13|14|15|16|17|18|19|20 |
| message|00|00|00|00|00|00|00|00|00|00 |
------------------------------------------
To change a message, move the cursor along until it flashes beneath the required
output 11-20 window.If the message required is between 0-9, enter it directly using the
numbered keys, or using the + or – keys step to the message number required between
00 and 15.