Page 27
IBVR20 software 8.43.doc
Issue 1
Inputs 2-10 may be individually selected to 1 of 4 modes.
Mode 00 Normally open (de energized) sounder circuit latching input.
Mode 01 Normally open (de energized) sounder circuit non latching input.
Mode 02 Normally closed (energized) fail safe latching input.
Mode 03 Normally closed (energized) fail safe non latching input.
To change the mode, move the cursor along until it flashes beneath the required fire
panel input.
Use keys 0-3 to select mode.
19. Press the Page down key again.
The display steps to the 2
nd
page of fire panel interface mode settings, inputs 11-20.
------------------------------------------
| F/P input|11|12|13|14|15|16|17|18|19|20 |
| input mode|00|00|00|00|00|00|00|00|00|00 |
------------------------------------------
Inputs 11-20 may be individually selected to 1 of 4 modes.
Mode 00 Normally open (de energized) sounder circuit latching input.
Mode 01 Normally open (de energized) sounder circuit non latching input.
Mode 02 Normally closed (energized) fail safe latching input.
Mode 03 Normally closed (energized) fail safe non latching input.
To change the mode, move the cursor along until it flashes beneath the required fire
panel input.
Use keys 0-3 to select mode.
20. Press the Page down key again.
The display steps to the 1
st
page of fire panel input 02 message selection, outputs 01-
10.
------------------------------------------
| F/P 02 out|01|02|03|04|05|06|07|08|09|10 |
| message|01|02|02|02|02|02|00|00|00|00 |
------------------------------------------
When the fire panel input receives an alarm condition, any of the outputs can be
selected to broadcast any message.
In the example above, if input 2 receives an alarm condition, output 01 will receive
message 1, outputs 02, 03, 04, 05 & 06 will receive message 2 and outputs 07, 08, 09 &
10 will be silent.
Any of the 7 available messages 01 – 07 can be selected but in addition when sounder
circuits using continuous output for evacuate and pulsing (1 sec on 1 sec off) for alert,
messages 2-7 can be selected for the alert and message 1 for the evacuate.
Note the latching mode must be used, see section 17.