GFCI Protection

Your spa may be equipped with a GFCI Protection 
feature. If your spa does have this feature enabled, the 
GFCI Trip Test must occur to allow proper spa function.

Within 1 to 7 days after startup, the spa will trip 
the GFCI to test it. (The number of days is factory 
programmed.) The GFCI must be reset once it has been 
tripped. After passing the GFCI Trip Test, subsequent 
GFCI trips will indicate a ground fault or other unsafe 
condition requiring the power to the spa to be shut off.

GFCI Trip Test Procedure

The installer can cause the GFCI Trip Test to 
occur sooner by initiating it with the following 
button sequence.

Press “Warm”, then “Jets 1”, then “Light.” (Each press 
must be within 3 seconds of the previous press.) Press 
the “Warm” button repeatedly until “

” is displayed. 

Press “Jets 1” to select it. Press the “Warm” button until 

” is displayed. Press “Jets 1” to initiate the GFCI 

Trip Test.

The GFCI should trip within several seconds and the spa 
should shut down. If it does not, shut down the power 
and manually verify that a GFCI breaker is installed and 
that the circuit and spa are wired correctly. Verify the 
function of the GFCI with its own test button. Restore 
power to the spa and repeat the GFCI Trip Test.

Once the GFCI is tripped by the test, reset the GFCI and 
the spa will operate normally from that point. You can 
verify a successful test by navigating to the “

” item 

as described above, pressing “Jets 1” and then pressing 
the “Warm” button until you see “

”. The code 

signifies GFCI Status - Passed.

The system will exit this menu in 30 seconds if no 
buttons are pressed.

Warning: 

The Owner should test and reset the GFCI 

on a regular basis to verify its function.

Note:

 

The GFCI section does not apply on EL systems used outside the United States. 

This GFCI section does not apply to GL Systems.

Summary of Contents for GL Series

Page 1: ...h gh gh gh gh gh gh ght t h h h h h h h h h ht t t t t t t t t t t M M M Mo Mo Mo Mo Mo Mo Mo Mo Mod d d de de de de de de de de de Heat Heat Warm Light Warm Jets 1 Jets 2 Light Mode Cool Blower Note...

Page 2: ......

Page 3: ...automatically Certain conditions filters or freeze can cause a function to operate longer while faults can cause a function to operate for a shorter length of time The system keeps track of timeouts r...

Page 4: ...n this case press any other button to exit System will revert to previous mode after 1 hour Jets 1 Press the Jets 1 button once to turn pump 1 on or off and to shift between low and high speeds if equ...

Page 5: ...for details Locking Features If this panel is used as the main panel locking features will not be available If this panel is used as a remote or additional panel it will lock when the main panel is l...

Page 6: ...military format 00 00 is midnight 23 00 is one hour before midnight When set to time is displayed in 12 hour am pm format 12 00 is midnight 11 00 pm is one hour before midnight Clean up Cycle Duration...

Page 7: ...o select it Press the Warm button until is displayed Press Jets 1 to initiate the GFCI Trip Test The GFCI should trip within several seconds and the spa should shut down If it does not shut down the p...

Page 8: ...nce the heater has cooled reset by pushing any button If spa does not reset shut off the power to the spa and call your dealer or service organization DO NOT ENTER THE WATER Remove the spa cover and a...

Page 9: ...e and return to normal operation Temperature display is current after pump has been running for at least 2 minutes will appear solid on the display when the temperature is not current will alternate w...

Page 10: ...tructions Every 30 days Test reset GFCI per manufacturer s instructions Every 90 days Drain and refill spa per manufacturer s instructions Every 180 days Clean and condition cover per manufacturer s i...

Page 11: ...s installed press the Fiber button once to start the light and wheel press it again to stop the wheel and then again to turn the light off The fiber icon stands still when the fiber optic light is on...

Page 12: ...e spa s 2EAD THE INSTRUCTION MANUAL s DEQUATE DRAINAGE MUST BE PROVIDED IF THE EQUIPMENT IS TO be installed in a pit s OR USE ONLY WITHIN AN ENCLOSURE RATED 3 NCLOSURE s ONNECT ONLY TO A CIRCUIT PROTE...

Reviews: