INTRODUCTION
I-E96-203C
D - 1
APPENDIX D - NIMP01 AND NIMP02 CONFIGURATION
INTRODUCTION
The IMMFP03 and IMMFP03B Multi-Function Processor Mod-
ules, through the IMMPI01 Multi-Function Processor Inter-
face Module, can use the NIMP01 and NIMP02 termination
modules for termination. Jumpers on the NIMP01 termina-
tion module configure the two RS-232-C ports for data termi-
nal equipment (DTE) or data communication equipment
(DCE). One of the RS-232-C ports can be configured as an
RS-485 port. The NIMP02 termination module is required
when installing redundant MFP modules. Refer to the
NIMP01 and NIMP02 product instruction for complete infor-
mation on termination module applications.
Figures
through
show the jumper configurations for
jumpers J1 and J2. Figure
shows the jumper configura-
tions for jumpers J5 through J10, J19 and J20. Figure
shows the jumper configurations for jumpers J14 through
J17. Figure
shows the NIMP01 connector and jumper
locations. Figure
shows the cable connections for a single
IMMFP03 or IMMPI01 module. Figure
shows the cable
connections for redundant IMMPI01 and IMMFP03 modules.
Jumpers J11 and J12 are storage posts for extra jumpers.
Jumper J13 is normally set with pins one and two connected.
Jumper J18 configures the terminal serial port for RS-485
operation when pins two and three are connected and con-
nector P7 is used instead of connector P5.
NOTES:
1.
RS-232-C port connections on the termination module are
through DB-9 connectors. Use Elsag Bailey cable NKMR02 to con-
nect a standard piece of equipment (computer or printer with a
DB-25 connector) to the termination module.
2.
There are no jumper settings on the NIMP02 termination mod-
ule. Refer to Figure
for cable connections.