INSTALLATION
INSTALLING THE TERMINATION UNIT/MODULE
I-E96-221A
3 - 11
3. If the system does not require -30 VDC, disconnect the -30
VDC supply wiring faston or set jumper J12 before installing
the IMCPM02 module.
4. Set jumper J12 correctly.
5. If you require additional information and/or assistance,
please contact Bailey Controls technical support.
6. Before installing the module, check all dipswitch and
jumper settings, and ensure that respective module cables are
attached to the MMU backplane.
Modules can be installed and removed under power. Installing
the module with power applied causes the Status LED to turn
red momentarily and then turn green. If it does not, refer to
.
To install module:
1. Guide the top and bottom edges along the top and bottom
rails of the MMU backplane.
2. Slide the module into the slot. Push it until the rear edge is
firmly seated in the backplane connectors.
3. Turn the two concentric screws ½ turn clockwise to lock
the modules in place.
INSTALLING THE TERMINATION UNIT/MODULE
For permanent mounting, the IMCPM02 module can connect
to a termination unit or termination module. Refer to
and
(NIMP01 module and NTMP01
unit) for information about these termination devices.
CAUTION
It is strongly recommended that cabinet power be turned off
before doing any termination unit wiring. Failure to do so could
result in equipment damage. Do not apply power until all wire
connections are verified. Do not apply power to the termination
unit when uncut dipshunts are installed. This may result in
damage to the termination unit.
ATTENTION
Il est fortement recommandé de mettre l'armoire hors tension
avant de procéder au câblage de la carte de raccordement afin
d'éviter tout dommage matériel. Ne rétablissez pas l'alimenta-
tion avant d'avoire vérifié toutes les connexions. Ne mettez pas
la carte de raccordement sous tension tant que les dipshunts
ne sont pas coupés, sinon la carte de raccordement pourrait
étre endommagée.