INSTALLATION
WIRING CONNECTIONS AND CABLING
I-E96-207A
3 - 9
into the backplane slot in the same slot as the one assigned to
the module. The latches should snap securely into place.
3. Align the module with the guide rails in the MMU; gently
slide the module in until the front panel is flush with the top
and bottom of the MMU frame.
4. Push and turn the two captive retaining latches on the
module faceplate one half turn to the latched position. It is
latched when the slots on the latches are vertical and the open
ends face the center of the module. (To remove the module,
turn the module retaining latches to the unlatched position
and gently slide it out).
WIRING CONNECTIONS AND CABLING
NOTE: Modules may be removed from the Module Mounting Unit
while the system is energized.
The COM has two card edge connectors to supply logic power
and provide I/O (P1 and P3 respectively).
Wiring
Installing the module in the MMU connects the controller to
the logic power, necessary to drive the circuitry, at P1. It will
also connect P3 to the I/O for communication with the field
devices. P1 and P3 connection require no additional wiring or
cabling.
Cable Connections
The IMCOM03/04 use either an NTCS02 or NICS01 for termi-
nation. Connect the controller module to the controller termi-
nation unit (TCS) with the NKTU01 cable. The J1 end of the
cable attaches to connector P1 on the TCS. The J2 end of the
cable attaches to the P3 card edge connector of the controller
module. See Figure
to determine the cables to use with the
termination unit or module you are using.
PREOPERATING ADJUSTMENTS
You do not have to make any adjustments to the COM prior to
operating.
CAUTION
Do not remove the cable from the module or the termination
unit while the INFI 90/Network 90 System is energized. Damage
to the module may result.