INSTALLATION
SAFETY RELATED INFORMATION
3 - 2
I-E96-207A
®
3. File a claim for any damage with the transportation com-
pany that handled the shipment.
4. Use the original packing material and container to store the
hardware.
5. Store the hardware in an environment of good air quality,
free from temperature and moisture extremes.
NOTE: Version 03 has one ROM chip (UX3). Version 04 has two
ROM chips (UX3,UX4).
SAFETY RELATED INFORMATION
Part of the required installation of the controller is the proper
selection of the hardware output default conditions and config-
uration of output default conditions. Typically, the hardware
and configuration default settings will be identical. However,
they must be defined separately. The hardware defaults are set
through switches on the controller module. The configuration
defaults are set through the logic with function codes. These
default values must be selected to provide a process condition
that is least likely to cause injury or equipment damage.
SETUP/PHYSICAL INSTALLATION
Prior to installation, you must set the module dipswitches and
install jumpers to configure the I/O. You must configure the
Termination Unit (TU) or Termination Module (TM) to accept
the field device signals and output the COM signals to the
process.
WARNING
The module is shipped with the default switches in the open or
non-operable state. The module digital outputs are de-ener-
gized (off) during start-up, during operator selected RESET,
configure mode and for certain failure conditions.
Analog outputs always hold last value when the module is put
into configure mode and go to user-selected values during
start-up, during operator selected RESET, and for certain fail-
ure conditions. These values must be selected by the end user
to prevent personal injury, equipment damage or damage to
the product.
AVERTISEMENT
French translation to be supplied later.