INTRODUCTION
SPECIFICATIONS (continued)
1 - 8
I-E96-207A
®
SPECIFICATIONS
(continued)
Operating
(continued)
Digital Outputs
Maximum on current
Maximum off current
Maximum on voltage
Analog Outputs
Linearity
Repeatability
Accuracy
(including above)
Resolution
Temperature Effect
Output Compliance
Maximum Load Inductance
4 Digital Outputs: 24 VDC
(Isolated, open-collector type)
150 mA
10
µ
A
1.5 V at 150 mA
2 Analog Outputs: 1 to 5 VDC, 4 to 20 mA
±
0.1% of span
±
0.05% of span
±
0.15% of span (voltage mode)
±
0.25% of span (current mode)
10 bit
±
0.004% of span per
o
C
600 Ohms
600 mH
Environmental
Electromagnetic/
Radio Frequency
Interference
Ambient Temperature
Atmospheric Pressure
Humidity
Air Quality
Values are not available at this time.
Keep cabinet doors closed. Do not use communication equipment
any closer than 2 meters from the cabinet.
0
o
to 70
o
C (32
o
to 158
o
F)
Sea level to 3 km (1.86 miles)
5% to 90% RH (
±
5%) up to 55
o
C (noncondensing)
5% to 40% RH (
±
5%) at 70
o
C (noncondensing)
Noncorrosive
Mounting
Each module occupies one slot in the INFI 90 Module Mounting
Unit (MMU).
Certification
CSA certified for use as process control equipment in an ordinary
(nonhazardous) location.
Specifications subject to change without notice.