MGS-150 Manual
6309-9000 Rev 2
23
Section 6. Functional Tests and Calibration
6.1. Introduction
To comply with the requirements of EN378 and the European F-GAS
regulation, sensors must be tested annually. However, local regulations
may specify the nature and frequency of this test.
CAUTION:
Check local regulations on calibration or testing
requirements.
CAUTION:
The MGS contains sensitive electronic
components that can be easily damaged. Do not touch nor
disturb any of these components
NOTE:
The MGS is calibrated at the factory. After
installation, a zero adjustment maybe required due to
differences in environmental conditions.
IMPORTANT:
If the MGS is exposed to a large leak it should
be tested to ensure correct functionality by electrically
resetting the zero setting and carrying out a bump test. See
procedures below.
IMPORTANT:
Bacharach recommends annual checks and
gas calibration. Bacharach also recommends sensor
replacement every 3 years or as required. Calibration
frequency may be extended based on application, but should
never exceed 2 years.
IMPORTANT:
In applications where life safety is critical,
calibration should be done quarterly (every 3 months) or on a
more frequent basis. Bacharach is not responsible for setting
safety practices and policies. Safe work procedures including
calibration policies are best determined by company policy,
industry standards, and local codes.
Summary of Contents for MGS-150
Page 10: ...MGS 150 Manual 10 6309 9000 Rev 2 Figure 2 EC or IR Sensor Components and Wiring...
Page 11: ...MGS 150 Manual 6309 9000 Rev 2 11 Figure 3 SC Sensor Components and Wiring...
Page 18: ...MGS 150 Manual 18 6309 9000 Rev 2 Figure 5 IP66 Housing with Splashguard...
Page 33: ...MGS 150 Manual 6309 9000 Rev 2 33...
Page 34: ...MGS 150 Manual 34 6309 9000 Rev 2...