3. INSTALLATION
3.1. Sensor Mounting Heights
Gas
Applications / Types
Suggested Mountings
Carbon Monoxide
Gas engine exhaust
4’ to 6’ from the floor
Nitric Oxide
Diesel engine exhaust
applications
Nitrogen Dioxide
Sulfur Dioxide
All
6” from the floor or near likely
spot for leakage
Refrigerants All
Combustibles
Propane
Methane
On/near ceiling (within 12”)
Hydrogen
NOTE:
Bacharach considers 4 to 6 feet from the floor as the “breathing
zone” when it applies to sensors installed for vehicle exhaust
applications.