GDC-350 Operation Manual
20
5909-9000
Rev
1
Functions
J6
J7
Resting (J7 jumpers are disabled)
P1
P1
Setting Span Gas Value (On-board Sensor)
P2
P2
Perform Zero (Null) Calibration (On-board Sensor)
P2
P3
Perform Span Calibration (On-board Sensor)
P2
P4
Adjust Low Gas Alarm Ascending Value (On-board Sensor)
P2
P5
Adjust High Gas Alarm Ascending Value (On-board Sensor)
P2
P6
Adjust Low Gas Alarm Descending Value (On-board Sensor)
P2
P7
Adjust High Gas Alarm Descending Value (On-board Sensor)
P2
P8
Enable/Disable Current Output
P2
P9
Setting Span Gas Value (Remote Sensor)
P3
P2
Perform Zero (Null) Calibration (Remote Sensor)
P3
P3
Perform Span Calibration (Remote Sensor)
P3
P4
Adjust Low Gas Alarm Ascending Value (Remote Sensor)
P3
P5
Adjust High Gas Alarm Ascending Value (Remote Sensor)
P3
P6
Adjust Low Gas Alarm Descending Value (Remote Sensor)
P3
P7
Adjust High Gas Alarm Descending Value (Remote Sensor)
P3
P8
Enable/Disable Current Output
P3
P9
Custom time delays for relays and internal audible alarm
(see page 23)
P4 N/A
Figure 4-2. J7 (Top) and J6 (Bottom) Jumper Banks