RFM-LR1

4

User Manual  v1.1

The first step you should take is to simply provision the network server. This can be any LoRa system that you 

would like to integrate the sensor with, with the AppEUI. 

 

The second step is to provision the application server with your unique DevEUI and AppKey. 

Digital activation process

1.

 Provision network server with AppEUI

2. 

Provision application server with unique DevEUI and AppKey

Alarms

The RFM-LR1 LoRa module have several alarm functions built in.  

When an alarm is detected the corresponding alarm flag in the status data is set. When any alarm flag is set 

the status, data is included in every report. The alarm flag must be reset manually using a Downlink command. 

Module removed

If the module is removed from the water meter after activation this alarm flag is set.

Magnetic fraud attempt

The module has a detector that can sense if a magnet is used to manipulate the function of a dry dial water 

meter. If a magnet is sensed the alarm flag is set.

Flow exceeds Q3

If the flow exceeds Q3 for more than 10 minutes the alarm flag is set. Q3 depends on the water meter (based 

on pipe) and should be configured using a Downlink command. The default Q3 value is based on the largest Q3 

for the specific series.

Leak detection

If a continuous flow has been detected for 24 hours the alarm flag is set. Two configurations parameters are 

used for this alarm, Leak window size and Leak zero tolerance, and these can be configured using Downlink 

commands. The leak window size defines how long it should be between the detected water meter movements 

to consider no flow.

Alarm reset

The alarm flags are reset by setting the Status data with a Downlink command. Setting it to 0 resets all alarms. 

Setting it to 0xFE resets alarm flag 0.

Summary of Contents for RFM-LR1

Page 1: ...deactivated The device activates when the red button is pressed for more than 8 seconds This happens automatically when the unit is mounted on to a GSD8 RFM mechanical water meter The following safety...

Page 2: ...essages are received The device tries to re join the network if it has not heard anything from the network for 288 uplinks 36 days Startup Sequence When the device has joined the network startup trans...

Page 3: ...al Physical installation process 1 Mount RFM LR1 unit on the water meter 2 Mount the locking pin and seal If you require further support please contact support bmeters com or your vendor Activating on...

Page 4: ...n this alarm flag is set Magnetic fraud attempt The module has a detector that can sense if a magnet is used to manipulate the function of a dry dial water meter If a magnet is sensed the alarm flag i...

Page 5: ...re key storage Battery life Battery life length 10 years at 4 hour intervals at SF12 Primary cell Lithium Manganese 3V Capacity 2 2 Ah Method Optical readout Using infrared diodes Weight Weight 85 g C...

Page 6: ...mands to be sent After approximately 2 minutes the device changes to Operational state Port Port 1 Payload 0x01 20 00 0x01 Data type 0x20 Status command 0x00 bit0 0 Normal startup bit1 0 No boot probl...

Page 7: ...o alarms 0x00 clears all alarms 0x80 clears all alarms except module removed etc 0x21 Volume Uint32 Big endian Liter Query Yes Volume as indicated on meter x 0 001 m3 0x22 Reporting interval Uint16 Bi...

Page 8: ...ting Module removed alarm flag Downlink 012000 Uplink 012000 Resets all alarm flags Downlink 012205A0 Uplink 012205A0 Sets the Reporting interval to 1440 minutes 24 hours Downlink 0227 Uplink 01270000...

Page 9: ...on slots parameters 0x05 RXParamSetupAns End device Acknowledges a RXSetupReq command 0x06 DevStatusReq Gateway Requests the status of the end device 0x06 DevStatusAns End device Returns the status of...

Reviews: