41
Additional phases require additional AC sources and TL983P modules.
2)
Front panel configuration
After verifying the TL983P adapters are properly wired on the rear panel, the AC sources
must be configured from the front panel. 3-phase operation is enabled by setting the
phase control field on each AC source.
The options for phase control are Master, Slave, or Disable. The master must be set first.
Any one of the three connected AC sources can be set to master. Use the directional key
pad to highlight the phase control field, use the soft key to select master, and press enter
to confirm (Figure 11.1).
Do not set more than one AC source to ‘Master’ as this may cause damage or a
malfunction.
RJ45 cables
Master
Figure 11.1: Phase control setting