background image

 

PD4-M-HCL 93006/93007 

50570_V1_Operation_Manual_PD4-M-
HCL_93006_93007_EN_080818 

 

Page 3 /  10 

 
1.3.1. Lightning zone A (main lightning) 

 
The  PD4-M-HCL  allows  you  to  compensate  for  differences  in 
brightness due to daylight coming from one side of a room fully 
automatically,  using  segmented  constant  light  regulation  in 
lighting  zone  A  across  3  groups.  Fittings  with  DALI  electronic 
ballasts are thus grouped as follows: 
 

 

Group 1: for areas with little daylight 
areas away from the windows 

 

Group 2: for neutral areas 
for example the central lighting run 

 

Group 3: for areas which may have strong daylight 
areas near the windows 

 
Groups 2 and 3 can be set up with a negative offset between 0% 
and 25%, and will then scale back their lighting output in relation 
to Group 1. In extreme lighting situations (very bright daylight or 
no daylight), both offset settings will be automatically reduced to 
0%. 

 
1.3.2. Lightning zone B and C (lectern or blackboard lightning) 

 
For teacher or blackboard lighting, lighting zone B (via DALI group 
4) and/or lighting zone C (via integrated relay) are available. 
In lighting zones B and C, automatic constant light regulation is 
disregarded. 

 
1.4. Integrated relay with operating modes 

 
There  are  7  different  operating  modes  available  on  the 
integrated  bistable  relay  (potential-free,  NO).  These  cannot  be 
combined: 
 

 

“Cut

-

off” –

 standby current consumption of connected DALI 

electronic ballasts is automatically minimised 

 

“HVAC” –

 heating, ventilation and air-conditioning units are 

automatically controlled for energy efficiency, depending on 
motion detection in the room, using a separately-set follow-
up time 

 

“Zone C” –

 activates lighting zone C with push button input 

C, for example to provide teacher or blackboard illumination 
without  a  DALI  electronic  ballast.  The  automatic  mode 
depends on the settings for lighting zone B (Group 4) 

 

“CdS”  –

 

“cadmium  sulfide”  –

  relay  works as  photo  electric 

switch 

 

“None” for “no function” –

 relay is not actuated 

 

“Alarm impulse” (via operating mode HVAC) –

 The relay only 

closes  for  2.5  seconds  if  at  least  3  movements  have  been 
detected during a time period of 9 seconds. This function can 
be  used  to  display  a  presence  in  the  room  on  external 
visualisations.  (Warning:  The  device  does  not  fulfil  the 
requirements of DIN EN50131-2-2 and therefore cannot be 
used in professional intrusion detection systems. 

 

“Impulse  function”  (via  operating  mode  HVAC)  –

  The 

impulse  function  can  be  used  to  control  external  HVAC 
systems. All 9 s will be set an impulse lasting 2.5 s 

 

 

 
1.5. Full automatic / semi-automatic mode 

 
Lighting zones A and B can be set individually to full automatic or 
semi-automatic  mode.  Lighting  zone  C  always  works  with  the 
settings from lighting zone B. In full automatic mode, the light is 
turned on automatically when motion is detected and ambient 
light is low enough, and turned off after an adjustable follow-up 
time  and/or  when  ambient  light  is  bright  enough.  Semi-
automatic mode works in a similar fashion, except that switching 
on the lights must take place via a push button (manual ON/ auto 
OFF). 

 
1.6. Push button functions 

 
Conventional NO push buttons can be used. 
A short press on all three push buttons, A, B and C, turns the light 
in each lighting zone on or off. A long press (> 2 seconds) on push 
buttons A and B leads to manual dimming (brightness up or down 

 another long press reverses the dimming direction). 

Special feature in full automatic mode: if you want to use a short 
press to deliberately switch off the light in the room, for example 
to show a film or set up a projector, the light remains off until the 
follow-up time has expired. 

Summary of Contents for PD4-M-HCL-FC

Page 1: ...gs 4 2 3 Potentiometer and DIP switches 4 2 4 Factory Reset 4 3 LED Indication 5 4 Bidirectional Smartphone App 5 4 1 Preparing smartphone Android Samsung iOS 5 4 2 Preparing IR Adapter 5 4 3 Connect...

Page 2: ...rom warm to cold white This function is used for test or presentation purposes 1 2 2 Application profiles All profiles are designed to activate from morning to afternoon with increasing brightness and...

Page 3: ...rovide teacher or blackboard illumination without a DALI electronic ballast The automatic mode depends on the settings for lighting zone B Group 4 CdS cadmium sulfide relay works as photo electric swi...

Page 4: ...minimised HVAC 5 10 15 light independent HVAC occupancy control HVAC 30 40 50 60 120 light independent HVAC occupancy control with 5 min switch on delay OFF No relay control Moon Night mode 10 lux Se...

Page 5: ...ng IR Adapter The IR Adapter has an integrated rechargeable battery for power supply Please charge the adapter first by means of the micro USB cable included in delivery The battery being charged The...

Page 6: ...approx 3500 and 5500 Kelvin The School profile offers motivating light that supports learning During the day the brightness ranges between approx 350 and 500 lux and the colour temperature between ap...

Page 7: ...as Licht bewegungsunabh ngig bei Unterschreiten der eingestellten Einschaltschwelle ein Abh ngig von der eingestellten Einschaltschwelle ist eine Ein Ausschaltverz gerung aktiv Zone C The interface be...

Page 8: ...self test cycle remain valid Test mode The test mode is for determining the detection area Upon each detected movement the light is switched on HCL test mode The test mode is used to check the colour...

Page 9: ...ortant note for slave operation connect slave devices only after setting up addressing or else ensure that while auto addressing takes place all LEDs blinking quickly no one remains in any slave devic...

Page 10: ...the wall 9 2 Default settings To adjust a desired target value more easily it is recommended to pre set a value using the app and the parameter LUX or via potentiometer which serves as basis for adju...

Reviews: