1. Operation 

 

1.1. General 

 
The PD4-M-HCL is a highly sensitive ceiling-mounted occupancy 
detector  based  on  passive  infrared  motion  detection,  with 
integrated DALI controller, DALI power supply and push button 
control. 
If  people,  animals  or  other  heat  sources  move  within  the 
detection  area,  the  detector  can  dim  and  switch  any  DALI-
controlled  electronic  ballast-driven  lights,  taking  account  of 
ambient light levels, such that a predefined room lighting level is 
constantly maintained. Slave devices, type PD4-S-DAA4G, can be 
installed to expand the detection area. 
 

1.2. Human Centric Lighting 

 
Human Centric Lighting (HCL) automatically changes the colour 
temperature and brightness of compatible DALI luminaires (DALI 
Device Type 8) during the day. This change takes place slowly and 
imperceptibly  in  small  steps.  The  lighting  is  based  on  natural 
daylight, which has a positive effect on well-being, performance 
and the natural sleep rhythm. 
 

1.2.1. HCL Mode  

 
Three modes can be selected under "HCL Mode": 

 

In  "Application  Profiles"  mode,  brightness  and  light 
temperature  are  automatically  changed  during  the  day 
based  on  a  defined  curve.  The  selection  of  the  profile 
suitable for the application is made in the next point.  

 

In "outdoor light sensor" mode, the light temperature of the 
luminaires follows the light temperature outdoors. For this 
purpose an external light sensor from B.E.G. - which is to be 
ordered separately - is required. The brightness can be freely 
selected. 

 

In  "Demonstration  Mode",  the  light  temperature  changes 
step by step from warm to cold white. This function is used 
for test or presentation purposes. 

1.2.2. Application profiles 

 
All profiles are designed to activate from morning to afternoon 
with  increasing  brightness  and  colour  temperature.  During 
lunchtime  and  from  late  afternoon,  the  activating  effect  is 
reduced. The lighting goes into the warm white area and to the 
lower light level. Overnight, the lighting remains at this setting. 
The  "Application profiles" are  optimised for  special  use.  Under 
"Application profiles" you can choose between three profiles: 

 

 

In  the  "Office"  profile,  the  brightness  during  the  day  is 
controlled  from  approx.  500  to  650  lux  and  the  colour 
temperature from approx. 3500 to 5500 Kelvin.  

 

In  the  "Industry"  profile,  the  brightness  during  the  day  is 
controlled  from  approx.  500  to  750  lux  and  the  colour 
temperature from approx. 3500 to 5500 Kelvin.  

 

In the "School" profile, the daytime brightness is controlled 
from  approx.  350  to  500  lux  and  the  colour  temperature 
from approx. 3500 to 5500 Kelvin. 

 

1.2.3. Date 

 
The  current  date  must  be  transferred from  the  smartphone  to 
the detector via the app. The integrated real-time clock can then 
control the application profiles. In the event of a power failure, 
the real-time clock is powered by an internal battery for at least 
48 hours. 

 
1.2.4. Time 

 
The  current  time  must  be  transferred from  the  smartphone  to 
the detector via the app. The integrated real-time clock can then 
control the application profiles. In the event of a power failure, 
the real-time clock is powered by an internal battery for at least 
48 hours. 

 
1.3. Groups and lighting zones 

 
There  are  three  lighting  zones  (areas  for  a  lighting  purpose) 
available which can be parameterised by means of a predefined 
grouping  principle  of  the  integrated  DALI  control  unit  and  an 
operating mode of the integrated relay. 
 
 
 

 

 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for PD4-M-HCL-FC

Page 1: ...gs 4 2 3 Potentiometer and DIP switches 4 2 4 Factory Reset 4 3 LED Indication 5 4 Bidirectional Smartphone App 5 4 1 Preparing smartphone Android Samsung iOS 5 4 2 Preparing IR Adapter 5 4 3 Connect...

Page 2: ...rom warm to cold white This function is used for test or presentation purposes 1 2 2 Application profiles All profiles are designed to activate from morning to afternoon with increasing brightness and...

Page 3: ...rovide teacher or blackboard illumination without a DALI electronic ballast The automatic mode depends on the settings for lighting zone B Group 4 CdS cadmium sulfide relay works as photo electric swi...

Page 4: ...minimised HVAC 5 10 15 light independent HVAC occupancy control HVAC 30 40 50 60 120 light independent HVAC occupancy control with 5 min switch on delay OFF No relay control Moon Night mode 10 lux Se...

Page 5: ...ng IR Adapter The IR Adapter has an integrated rechargeable battery for power supply Please charge the adapter first by means of the micro USB cable included in delivery The battery being charged The...

Page 6: ...approx 3500 and 5500 Kelvin The School profile offers motivating light that supports learning During the day the brightness ranges between approx 350 and 500 lux and the colour temperature between ap...

Page 7: ...as Licht bewegungsunabh ngig bei Unterschreiten der eingestellten Einschaltschwelle ein Abh ngig von der eingestellten Einschaltschwelle ist eine Ein Ausschaltverz gerung aktiv Zone C The interface be...

Page 8: ...self test cycle remain valid Test mode The test mode is for determining the detection area Upon each detected movement the light is switched on HCL test mode The test mode is used to check the colour...

Page 9: ...ortant note for slave operation connect slave devices only after setting up addressing or else ensure that while auto addressing takes place all LEDs blinking quickly no one remains in any slave devic...

Page 10: ...the wall 9 2 Default settings To adjust a desired target value more easily it is recommended to pre set a value using the app and the parameter LUX or via potentiometer which serves as basis for adju...

Reviews: