background image

 

PD4-M-HCL 93006/93007 

50570_V1_Operation_Manual_PD4-M-
HCL_93006_93007_EN_080818 

 

Page 6 /  10 

 

Status LEDs 

The  status  LEDs  indicate 

  for  example  - 

movement.  PLEASE  NOTE:  In  opened  state 
and in test mode the status LEDs are ACTIVE. 

 

 
INI light 

The INI-ON / INI-OFF function defines if the 
light  is  on  (INI-ON)  or  off  (INI-OFF)  during 
self-test  cycle  (60s  after  mains  supply). 
Factory setting is INI-ON. 
 

 

Start Burn In Function 

Before  the  lamp  can  be  dimmed,  the 
dimming function has to be suppressed for a 
certain time in order to burn in the lamps. 
T5 fluorescent lamps: 80 h 
T8 fluorescent lamps: 100 h 
During this time, the detector only switches 
the  light  ON  or  OFF.  A  dimming  to  the  set 
value does not take place. 

 

5.3. Human Centric Lighting 

 

 

 

HCL Mode 

Human 

Centric 

Lighting 

(HCL) 

can 

synchronise the internal clock in rooms with 
low  daylight  supply  and  sustainably 
strengthen the  well-being.  By  changing  the 
brightness and the light temperature during 
the  day,  the  dynamics  of  daylight  are 
brought  into  the  building.  This  is  done  by 
application  profiles  or  via  an  external  light 
sensor.  A  demonstration  mode  is  available 
for testing purposes. 
 

 

 
Application profiles 

 

The "office" profile provides motivating 
light.  During  the  day,  the  brightness 
ranges between approx. 500 and 650 lux 
and  the  colour  temperature  between 
approx. 3500 and 5500 Kelvin.  

 

The 

"Industry" 

profile 

provides 

concentration-increasing  light.  During 
the day, the brightness ranges between 
approx. 500 and 750 lux and the colour 
temperature between approx. 3500 and 
5500 Kelvin.  

 

The  "School"  profile  offers  motivating 
light that supports learning. During the 
day,  the  brightness  ranges  between 
approx. 350 and 500 lux and the colour 
temperature between approx. 3500 and 
5500 Kelvin. 
 

 

Date 

Current date in the device. The current date 
from  the  mobile  is used when sending  this 
parameter.  
 

Time 

Current time in the device. The current time 
from  the  mobile  is used when sending  this 
parameter. 

 
 
 

 

5.4. Lighting 

 

 

Follow-up Time 

This  time  period  starts  upon  detected 
movement and defines the duration for the 
connected load to stay on. 
 

 

Brightness set value 

The  brightness  set  value  is  the  luminance 
value to which the brightness in the room is 
regulated.  To  define  the  set  value,  the 
desired brightness can be adjusted using the 
BRIGHTER/DARKER  button  and  can  be 
stored with the EYE button. Fine tuning can 
be achieved using the +/

 buttons. The value 

is stored automatically. 
 

5.5. DALI groups 1-3: lighting zone A 

 

 
Automatic 

The operation mode of the detector can be 
selected. FULL: In this operating mode, the 
lighting  switches  automatically  on  and  off 
for  increased  comfort,  depending  on 
presence  and  brightness.  SEMI:  In  this 
operating mode, the light turns on only after 
a manual switching, for an increased savings 
success.  Switching  off  is  automatically  or 
manually.In case  motion is detected  within 
the 10sec. after elapse of the follow-up time, 
the detector switches the light on again and 
the follow-up time starts again. If there is no 
motion detected within the 10s after elapse 
of  the  follow-up  time,  the  light  has  to  be 
turned on manually. 
 

 

Offset group 2 

Damping of group 2 relative to group 1 in % 
 

 

Offset group 3 

Damping of group 3 relative to group 1 in % 
 

Summary of Contents for PD4-M-HCL-FC

Page 1: ...gs 4 2 3 Potentiometer and DIP switches 4 2 4 Factory Reset 4 3 LED Indication 5 4 Bidirectional Smartphone App 5 4 1 Preparing smartphone Android Samsung iOS 5 4 2 Preparing IR Adapter 5 4 3 Connect...

Page 2: ...rom warm to cold white This function is used for test or presentation purposes 1 2 2 Application profiles All profiles are designed to activate from morning to afternoon with increasing brightness and...

Page 3: ...rovide teacher or blackboard illumination without a DALI electronic ballast The automatic mode depends on the settings for lighting zone B Group 4 CdS cadmium sulfide relay works as photo electric swi...

Page 4: ...minimised HVAC 5 10 15 light independent HVAC occupancy control HVAC 30 40 50 60 120 light independent HVAC occupancy control with 5 min switch on delay OFF No relay control Moon Night mode 10 lux Se...

Page 5: ...ng IR Adapter The IR Adapter has an integrated rechargeable battery for power supply Please charge the adapter first by means of the micro USB cable included in delivery The battery being charged The...

Page 6: ...approx 3500 and 5500 Kelvin The School profile offers motivating light that supports learning During the day the brightness ranges between approx 350 and 500 lux and the colour temperature between ap...

Page 7: ...as Licht bewegungsunabh ngig bei Unterschreiten der eingestellten Einschaltschwelle ein Abh ngig von der eingestellten Einschaltschwelle ist eine Ein Ausschaltverz gerung aktiv Zone C The interface be...

Page 8: ...self test cycle remain valid Test mode The test mode is for determining the detection area Upon each detected movement the light is switched on HCL test mode The test mode is used to check the colour...

Page 9: ...ortant note for slave operation connect slave devices only after setting up addressing or else ensure that while auto addressing takes place all LEDs blinking quickly no one remains in any slave devic...

Page 10: ...the wall 9 2 Default settings To adjust a desired target value more easily it is recommended to pre set a value using the app and the parameter LUX or via potentiometer which serves as basis for adju...

Reviews: