PD4-M-HCL 93006/93007
50570_V1_Operation_Manual_PD4-M-
HCL_93006_93007_EN_080818
Page 5 / 10
3. LED Indication
Nr. Indication
white
green
red
1
Self-test cycle
(factory setting)
Blinking
Blinking
Blinking
2
Self-test cycle
(not programmed)
-
-
Blinking
3
Self-test cycle
(programmed via IR)
-
-
Fast
blinking
4
Self-test cycle
(not prog
double locked)
-
Blinking
-
5
Self-test cycle
(programmed via IR +
double locked)
-
Fast
blinking
-
6
Too bright
-
Blinking
-
7
IR signal OK
Short
ON
-
-
8
DALI configuration
mode / grouping
process
ON
ON
ON
9
DALI autoaddressing
Fast
blinking
Fast
blinking
Fast
blinking
10 Broadcast mode
ON
-
-
11 Unlocked (parameters
+ commands)
-
ON
-
12 Movement detected
-
-
Short
ON
4. Bidirectional Smartphone App
4.1 Preparing smartphone (Android Samsung, iOS)
Please install the app
“
B.E.G. BiRC
”
, available in the respective
App Store. Depending on the end device it can be necessary to
update the operating system. For current system requirements
see application description.
4.2. Preparing IR-Adapter
The IR-Adapter has an integrated rechargeable battery for power
supply. Please charge the adapter first by means of the micro USB
cable (included in delivery). The battery being charged. The red
LED switches off when battery is full.
4.3. Connect Adapter with smartphone
Plug the adapter in to the audio socket of your Smartphone or
tablet. You must ensure that the IR-Adapter is fully inserted into
the socket.
Please note that covers or cases may partially block a correct
insertion of the adapter into the audio socket.
Set the volume of the audio socket to maximum in order to
ensure a sufficient transmission range of the IR signal.
5. Smartphone App Parameters
5.1. General
LEFT BUTTON
Select function of the right button
READ OUT
Read out bidirectional product
SEND
Send selected parameters to the device
SEND ALL
Send all parameters to the device
(PLEASE NOTE: all set parameters will be
overwritten, e.g. also the brightness
threshold)
5.2. Device
Software Version
Device PIN
Lock device
DALI Address
Sensitivity
A high (detection) sensitivity being selected,
even smaller movements will be detected
and larger surfaces will be monitored.
Reflection factor