Azbil MY8045A Specifications & Instructions Download Page 6

AB-6682 

Universal bracket (Part No. 12596-0001) 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 3.  Dimensions (mm): Universal bracket 

Note: 

Universal bracket is supplied with the product.  Additionally order only when necessary. 

 

 

Parts Identification 

 

 

 

 

 

 

 

 

Figure 4.  Parts identification 

 

 

2 pan-head tapping screws (slotted, M4 

×

 12, 1.4 pitch)

equivalent to JIS* B 1115-1976 are attached to the 
universal bracket. 
 
   

JIS: Japanese Industrial Standards 

229

R2.2

20 

12 

5

7

R2.2

R2.2 

R2.2

5

10

23

35

47

58.25

71 

83 

105 

Service pin switch 
(Manual switch) 

Summary of Contents for MY8045A

Page 1: ...ler Manual open close function allows easy adjustment without power supply Torque limit circuit inside the actuator automatically stops the damper in fully closed or open positions Low power consumpti...

Page 2: ...that keeps product operating cycle excessively frequent Overuse of the product may shorten the product service life Installation and wiring must be performed by qualified personnel in accordance with...

Page 3: ...el WY5117C Infilex GC Model WY5111 Infilex GD Model WY5110 PMX III Model WY2001 Infilex FC Model WY5205 Infilex VC Model WY5206 Neopanel Model QY7205 Digital user terminal Neoplate Model QY7290 Analog...

Page 4: ...500 V AC for 1 min 1 mA or less Control signal SAnet Communication Transmission system Voltage transmission SAnet via SAnet Transmission speed 1200 bps Transmission distance Transmission distance var...

Page 5: ...6682 5 Dimensions Actuator Figure 2 Dimensions mm Damper actuator Clearance for maintenance 148 5 248 98 97 5 200 57 50 100 10 188 49 5 1 6 5 Clearance for maintenance 28 12 5 5 67 10 100 188 80 9 10...

Page 6: ...itionally order only when necessary Parts Identification Figure 4 Parts identification 2 pan head tapping screws slotted M4 12 1 4 pitch equivalent to JIS B 1115 1976 are attached to the universal bra...

Page 7: ...of the actuator and fix the bracket onto the damper with the two M4 tapping screws Figure 6 Installation of the actuator with forward rotation to min 95 mm long shaft 2 3 Confirm that the damper shaf...

Page 8: ...R side outward Figure 10 Installation of the actuator with reverse rotation to 20 95 mm long shaft Wiring CAUTION To prevent product damage always disconnect the power supply from the product before p...

Page 9: ...SAnet ID on the SAnet ID label and address number to set The SAnet ID label is attached on a side surface of the actuator as shown in Fig 12 Figure 12 Locations of the labels IMPORTANT Address settin...

Page 10: ...actuator and the actual damper position agree synchronize Note that Synchronisation is performed by our service personnel To our service personnel Refer to Engineering Manual of Intelligent Component...

Page 11: ...haft Insert the accessory hexagon wrench to the hexagonal hole provided on the front surface of the damper actuator Rotate the wrench to open direction until the lock is released Once the lock is rele...

Page 12: ...AB 6682 Specifications are subject to change without notice Building Systems Company http www azbil com Rev 1 1 Jul 2012 AB 6682 J AI 6682 Rev 1 0 12...

Reviews: