AB-6682
3
System Configurations
Notes:
∗
MIS may be used instead of SMS and DSS for your system. Note that MIS cannot be mixed with SMS or DSS in the same system.
∗
Up to two SAnet I/F (interface) modules can be connected to one Infilex GC/Infilex GD.
∗
For detailed specifications of SAnet, refer to
Installation Manual of Intelligent Component Series for SAnet Communication
(AB-6713).
∗
1 damper actuator or 1 ACTIVAL requires 1 SAnet address. 1 ACTIVAL PLUS requires 2 SAnet addresses.
Figure 1. System configuration example: SAnet connection in savic-net
™
FX system
Client PC
SCS
SMS
Infilex
™
AC
Model WY5117C
Infilex
™
GC
Model WY5111
Infilex
™
GD
Model WY5110
PMX-III
Model WY2001
Infilex
™
FC
Model WY5205
Infilex
™
VC
Model WY5206
Neopanel
Model QY7205
(Digital user terminal)
Neoplate Model QY7290
(Analog user terminal)
NC-bus (Max. 25 units and 500 m, but extendable up to 1000 m with the repeater module.)
SC-bus (Max. 50 units and 1000 m)
BACnet
®
/IP
Infilex
™
SC
Model WY5207W
Neopanel
Model QY7205
(Digital user terminal)
DSS
MIS
SAnet
I/F
Intelligent Component
Series
ACTIVAL
™
Infilex
™
ZM
Model WY5122
SAnet (Max. 15 addresses)
Intelligent Component
Series
Damper actuator
Display Panel
Intelligent Component
Series
ACTIVAL
™
PLUS
Temperature sensor
for pipe surface
DSS: Data Storage Server
MIS: Management Integration Server
PMX-III: PARAMATRIX
™
-III
SCS: System Core Server
SMS: System Management Server