System Indication Label
System indication label is attached to the front surface of the product. Write down the name of the SAnet system, host controller
number of the SAnet system, SAnet line number, and address.
Figure 13. SAnet system indication label
Adaption (Setting Rotating Angle)
CAUTION
•
Before performing Adaption, check that the rotating direction of the product is correct.
When the rotation angle of the actuator is adjusted or changed, the actuator needs to memorize (adapt) the adjusted/changed
rotation angle. Note that Adaption is performed by our service personnel.
(To our service personnel: Refer to
Engineering Manual of Intelligent Component Series for SAnet Communication
(AB-6685))
Synchronisation (Position Alignment)
Damper position which the actuator controls disagrees with the actual damper position if actuator mounting position on the shaft
is changed. In such a case, the actuator requires Synchronisation so that the damper position controlled by the actuator and the
actual damper position agree (synchronize). Note that Synchronisation is performed by our service personnel.
(To our service personnel: Refer to
Engineering Manual of Intelligent Component Series for SAnet Communication
(AB-6685))
Setting of the Maximum Rotation Angle
To set the maximum rotation angle of the damper actuator to 90
°
or narrower, use the mechanical stopper supplied with the
product. The mechanical stopper allows to set every 5
°
increment within 30
°
to 90
°
range.
Setting procedure
1) Attach the mechanical stopper to a position according to the range to be set. Insert the mechanical stopper into grooves
provided on the damper actuator, as shown in the figure below.
2) Fix the mechanical stopper with the accessory tapping screw. There are 3 tapped holes (indicated with ‘x’) provided on the
scale of the damper position. Insert the tapping screw into either one of the holes, through the mechanical stopper.
Figure 14. Mechanical stopper
Write down the following.
•
SYSTEM NAME:
System name or device number
•
CON No.:
Host controller number
(Infilex GC/Inifilex GD number)
•
SAnet No.:
SAnet line number
•
ADDRESS:
SAnet address
System indication label
SAnet ID label
30 to 90
°