System Indication Label 

System indication label is attached to the front surface of the product.  Write down the name of the SAnet system, host controller 
number of the SAnet system, SAnet line number, and address. 

 

 

 

 

 

 

 

 

 

Figure 13.  SAnet system indication label 

 
Adaption (Setting Rotating Angle) 

  CAUTION 

 

  Before performing Adaption, check that the rotating direction of the product is correct. 

 

When the rotation angle of the actuator is adjusted or changed, the actuator needs to memorize (adapt) the adjusted/changed 
rotation angle.  Note that Adaption is performed by our service personnel. 

(To our service personnel: Refer to

 Engineering Manual of Intelligent Component Series for SAnet Communication

 (AB-6685)) 

 
Synchronisation (Position Alignment) 

Damper position which the actuator controls disagrees with the actual damper position if actuator mounting position on the shaft 
is changed.  In such a case, the actuator requires Synchronisation so that the damper position controlled by the actuator and the 
actual damper position agree (synchronize).  Note that Synchronisation is performed by our service personnel. 

(To our service personnel: Refer to 

Engineering Manual of Intelligent Component Series for SAnet Communication

 (AB-6685))  

 

Setting of the Maximum Rotation Angle 

To set the maximum rotation angle of the damper actuator to 90

°

 or narrower, use the mechanical stopper supplied with the 

product.  The mechanical stopper allows to set every 5

°

 increment within 30

°

 to 90

°

 range. 

Setting procedure 

1)  Attach the mechanical stopper to a position according to the range to be set.  Insert the mechanical stopper into grooves 

provided on the damper actuator, as shown in the figure below. 

2)  Fix the mechanical stopper with the accessory tapping screw.  There are 3 tapped holes (indicated with ‘x’) provided on the 

scale of the damper position.  Insert the tapping screw into either one of the holes, through the mechanical stopper. 

 

 

 

 

 

 

Figure 14.  Mechanical stopper 

 

Write down the following. 

 

 SYSTEM NAME: 

System name or device number 

 

 CON No.: 

Host controller number 
(Infilex GC/Inifilex GD number) 

 

 SAnet No.: 

SAnet line number 

  

 ADDRESS: 

SAnet address 

 

System indication label 

SAnet ID label 

30 to 90

°

 

Summary of Contents for MY8045A

Page 1: ...ler Manual open close function allows easy adjustment without power supply Torque limit circuit inside the actuator automatically stops the damper in fully closed or open positions Low power consumpti...

Page 2: ...that keeps product operating cycle excessively frequent Overuse of the product may shorten the product service life Installation and wiring must be performed by qualified personnel in accordance with...

Page 3: ...el WY5117C Infilex GC Model WY5111 Infilex GD Model WY5110 PMX III Model WY2001 Infilex FC Model WY5205 Infilex VC Model WY5206 Neopanel Model QY7205 Digital user terminal Neoplate Model QY7290 Analog...

Page 4: ...500 V AC for 1 min 1 mA or less Control signal SAnet Communication Transmission system Voltage transmission SAnet via SAnet Transmission speed 1200 bps Transmission distance Transmission distance var...

Page 5: ...6682 5 Dimensions Actuator Figure 2 Dimensions mm Damper actuator Clearance for maintenance 148 5 248 98 97 5 200 57 50 100 10 188 49 5 1 6 5 Clearance for maintenance 28 12 5 5 67 10 100 188 80 9 10...

Page 6: ...itionally order only when necessary Parts Identification Figure 4 Parts identification 2 pan head tapping screws slotted M4 12 1 4 pitch equivalent to JIS B 1115 1976 are attached to the universal bra...

Page 7: ...of the actuator and fix the bracket onto the damper with the two M4 tapping screws Figure 6 Installation of the actuator with forward rotation to min 95 mm long shaft 2 3 Confirm that the damper shaf...

Page 8: ...R side outward Figure 10 Installation of the actuator with reverse rotation to 20 95 mm long shaft Wiring CAUTION To prevent product damage always disconnect the power supply from the product before p...

Page 9: ...SAnet ID on the SAnet ID label and address number to set The SAnet ID label is attached on a side surface of the actuator as shown in Fig 12 Figure 12 Locations of the labels IMPORTANT Address settin...

Page 10: ...actuator and the actual damper position agree synchronize Note that Synchronisation is performed by our service personnel To our service personnel Refer to Engineering Manual of Intelligent Component...

Page 11: ...haft Insert the accessory hexagon wrench to the hexagonal hole provided on the front surface of the damper actuator Rotate the wrench to open direction until the lock is released Once the lock is rele...

Page 12: ...AB 6682 Specifications are subject to change without notice Building Systems Company http www azbil com Rev 1 1 Jul 2012 AB 6682 J AI 6682 Rev 1 0 12...

Reviews: